Description
Type
Error code
Item source failed to send positions to the controller. No re-
sponse from the controller.
Error
8342
The RobotWare version is later than the ABB Industrial Robot
Communication Runtime on the PC. The Communication
Runtime needs to be updated.
Error
8343
Solution: If possible update PickMaster to the latest version.
If this dose not solve the problem or for some reason is not
possible, update the ABB Industrial Robot Communication
Runtime on the PC.
The installation can be downloaded from the
, where it is included in the
Tools and
Utilities
package.
Failed to start program in Auto.
Error
8345
Possible reason: The RW role setting 'Remote start/stop
program in Auto' is not selected.
The motion server already exists as an instance (only one
instance is allowed).
Error
8393
The robot ID already exists (IDs shall be unique).
Error
8394
No robot defined with that ID.
Error
8395
Work areas still exist. The conveyor cannot be removed before
the work areas are removed.
Error
8396
Solution: Remove all work areas for the conveyor.
A work area with that ID already exists. (All IDs shall be
unique).
Error
8397
No work area with that ID exists. An operation was executed
on a non-existing work area. The work area has probably
been removed.
Error
8398
Settings on the work area failed due to a bad work area ID.
Error
8399
The system failed to apply new work area settings due to a
bad work area ID.
Error
8400
The system failed to set a new work area because the work
area ID does not exist.
Error
8401
The system failed to apply a new work area tune because the
work area ID does not exist.
Error
8402
The system failed to apply new robot settings because the
robot ID does not exist.
Error
8403
The system failed to set new robot settings because the robot
ID does not exist.
Error
8404
The system failed to set a new robot speed because the robot
ID does not exist.
Error
8406
Failed to update the work area due to wrong work area type
(indexed work area / conveyor work area).
Error
8407
There are no work areas defined for the robot.
Warning
8408
Solution: Define work areas and set up position sources for
the work areas for the robot before project start
Downloading elog files from controller.
Status
8418
Reason: If elog files are missing at production start they will
be downloaded automatically.
Continues on next page
Application manual - PickMaster® Twin - PowerPac
441
3HAC064218-001 Revision: B
© Copyright 2021 ABB. All rights reserved.
7 Troubleshooting
7.5 Error codes
Continued
Содержание PickMaster Twin - PowerPac
Страница 1: ...ROBOTICS Application manual PickMaster Twin PowerPac ...
Страница 2: ...Trace back information Workspace Main version a394 Checked in 2021 03 25 Skribenta version 5 4 005 ...
Страница 8: ...This page is intentionally left blank ...
Страница 12: ...This page is intentionally left blank ...
Страница 16: ...This page is intentionally left blank ...
Страница 420: ...This page is intentionally left blank ...
Страница 444: ...This page is intentionally left blank ...
Страница 446: ...This page is intentionally left blank ...
Страница 448: ...This page is intentionally left blank ...
Страница 452: ......
Страница 453: ......