OVR-15, 27 & 38 LV cabinet Instruction Manual
Default Shipment
Low Voltage (LV) control cabinet
Optional items
(only if ordered separately)
Mounting brackets
Auxiliary power cable (2x1.5 sq.mm)
Any additional spares
S
TORAGE OF RECLOSER
LV
UNIT
The LV Cabinet with complete packing should always be stored indoor to protect from direct sunlight &
rain or snow. The LV cabinet should be stored in its original transport units, where they are well
protected from damage.
LV cabinet can be stored up to 3 months from date of shipment from the factory. For longer storage, the
packing needs to be removed and the recloser to be kept under controlled environmental conditions.
We define storage in controlled conditions as a place with:
-
Leak proof roof
-
Solid, flat ground
-
Relative humidity less than 50%
-
Temperature 20
0
C (+10
o
C)
-
The heating elements must be connected to the electric supply to protect the control equipment
from corrosion or freezing damage.
The LV cabinets must be stored in the upright position to avoid moisture accumulation.
Recommended storage temperature range is -20 Deg C to + 40 Deg C.
The LV control cabinet has rechargeable batteries inside. A periodic check of battery
voltage (24V) & periodic charging of the batteries (typically every three months) may be
required in case of prolonged storage. For the batteries in your control cabinet, refer to
technical documentation of the respective battery manufacturer. Also refer the section
“Inspection & Maintenance” for further information.
If the LV cabinet is not placed in service immediately, it is essential that proper care be
exercised in handling and storage to ensure good operating condition in the future.
Please consult ABB if the recloser will be in storage for an extended period of time
before installation.