8 |
P a g e
OVR-15, 27 & 38 LV cabinet Instruction Manual
Also, as improvements in assemblies and parts are made, some parts may differ in appearance that
depicted in illustrations; however, functionality will be equivalent.
E.
W
ORKING ON
LV
CABINETS AND MANDATORY SAFETY
PROCEDURES
.
Whenever it is required to work on LV Cabinet, it is mandatory to follow following minimum procedures:
a.
Isolate the recloser from power system on its both sides. Put recloser in OPEN condition by
operating the emergency manual trip handle (yellow handle).
b.
Confirm the OPEN status of the recloser from the mechanical ON/OFF indicator, from SLD on LCD
display & the indication LEDs on RER615 HMI.
c.
Always put the SERVICE /DISCHARGE selector switch in the LV cabinet to DISCHARGE position.
d.
Follow the safety warning instructions on various warning labels provided on the LV & HV units
e.
Remove the control cable from both HV & LV cabinets & cover the 24 pin male connectors by plastic
caps provided.
Although warning hazards are related to personal injury, it is necessary to understand that under certain
operational conditions, operation of damaged equipment may result in degraded process performance
leading to personal injury or death. Therefore, comply fully with all warning and caution notices.