36 |
P a g e
OVR-15, 27 & 38 LV cabinet Instruction Manual
13
RER615
S
ETTINGS
T
ABLE
5.1
:
S
ETTINGS FOR
RER615
WITH REFERENCE TO
OVR-15,
27
&
38
RECLOSER
Sr.
No.
Protection
IEC61850
Identification
Setting range
available in
RER615
For OVR-15 Recloser
600/1A CT & 15.5kV System Voltage
For OVR-27 Recloser
600/1A CT & 27kV System Voltage
For OVR-38 Recloser
600/1A CT & 38kV System Voltage
Setting Range to be
used
(in Nominal Values)
Setting Range to be
used
(in Absolute Values)
Setting Range to be
used
(in Nominal Values)
Setting Range to be
used
(in Absolute Values)
Setting Range to be
used
(in Nominal Values)
Setting Range to be
used
(in Absolute Values)
1
Three-phase non-directional overcurrent protection (FPHxPTOC) main settings
Start Value
FPHLPTOC
0.05...5.00 × In
0.05...5.00 × In
30-3000A
0.05...5.00 × In
30-3000A
0.05...5.00 × In
30-3000A
PHHPTOC
0.10...40.00 × In
0.10…20.83 × In
60-12500A
0.10…20.83 × In
60-12500A
0.10…26.6 × In
60-16000A
PHIPTOC
1.00...40.00 × In
1.00…20.83 × In
600-12500A
1.00…20.83 × In
600-12500A
1.00...26.6 × In
600-16000A
Time multiplier
FPHLPTOC
0.05...15.00
0.05...15.00
30-9000A
0.05...15.00
30-9000A
0.05...15.00
30-9000A
PHHPTOC
0.05...15.00
0.05...15.00
30-9000A
0.05...15.00
30-9000A
0.05...15.00
30-9000A
Operate delay time
FPHLPTOC
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
PHHPTOC
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
PHIPTOC
20...200000 ms
20...200000 ms
20...200000 ms
20...200000 ms
20...200000 ms
20...200000 ms
20...200000 ms
2
Optional Three-phase directional overcurrent protection (FDPHxPDOC) main settings
Start Value
FDPHLPDOC
0.05...5.00 × In
0.05...5.00 × In
30-3000A
0.05...5.00 × In
30-3000A
0.05...5.00 × In
30-3000A
DPHHPDOC
0.10...40.00 × In
0.10…20.83 × In
60-12500A
0.10…20.83 × In
60-12500A
0.10…26.6 × In
60-16000A
Time multiplier
DPHxPDOC
0.05...15.00
0.05...15.00
30-9000A
0.05...15.00
30-9000A
0.05...15.00
30-9000A
Operate delay time
DPHxPDOC
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
40...200000 ms
Directional mode
DPHxPDOC
1 = Non-
directional
1 = Non-directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
1 = Non-
directional
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
2 = Forward
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
3 = Reverse
Characteristic angle
DPHxPDOC
-179...180°
-179...180°
-179...180°
-179...180°
-179...180°
-179...180°
-179...180°
3
Non-directional earth-fault protection (FEFxPTOC) main settings
Start Value
FEFLPTOC
0.010...5.000 × In
0.010...5.000 × In
6-3000A
0.010...5.000 × In
6-3000A
0.010...5.000 × In
6-3000A
EFHPTOC
0.10...40.00 × In
0.10…20.83 × In
60-12500A
0.10…20.83 × In
60-12500A
0.10…26.6 × In
60-16000A
EFIPTOC
1.00...40.00 × In
1.00...20.83 × In
600-12500A
1.00...20.83 × In
600-12500A
1.00...26.6 × In
600-16000A
Time multiplier
FEFLPTOC
0.05...15.00
0.05...15.00
30-9000A
0.05...15.00
30-9000A
0.05...15.00
30-9000A