14
Start-Up
Encoder
This group defines the setup for encoder use:
• Set the number of encoder pulses per shaft revolution.
• Enable the encoder operation.
• Defines how mechanical angle and revolution data is reset.
Note!
a check under the heading “S” indicates that the parameter can
only be modified when the drive is stopped.
Group 50: Encoder
Code Description Range
Resolution
Default
S
5001
PULSE NR
0…16384 ppr
1
1024
9
Sets the number of pulses provided by an optional encoder for each full motor shaft revolution.
5002
ENCODER ENABLE
0, 1
1
0
9
Enables/disables optional external encoder.
0 =
DISABLE
– Drive uses speed feedback derived from the internal motor model (applies for
any setting of parameter 9904
MOTOR
CTRL
MODE
).
1 =
ENABLE
– Drive uses feedback from an optional encoder. This function requires the Pulse
Encoder Interface Module (OTAC-01) and an encoder. Operation depends on the setting of
parameter 9904
MOTOR
CTRL
MODE
:
• 9904 = 1 (
VECTOR
:
SPEED
), the encoder provides improved speed feedback and improved
low speed torque accuracy.
• 9904 = 2 (
VECTOR
:
TORQ
), the encoder provides improved speed feedback and improved
low speed torque accuracy.
• 9904 = 3 (
SCALAR
:
SPEED
), the encoder provides speed feedback. (This is not closed loop
speed regulation. However, using parameter 2608
SLIP
COMP
RATIO
and an encoder
improves steady state speed accuracy.)
5003
ENCODER FAULT
1, 2
1
1
9
Defines the drive response if the encoder signal is lost.
1 =
FAULT
– A fault is generated, and the motor coasts to a stop.
2 =
WARNING
– An alarm is generated and the ACS550 operates as is if parameter 5002
ENCODER
ENABLE
= 0 (
DISABLE
), that is, speed feedback is derived from the internal motor
model.
5010
Z PLS ENABLE
0, 1
1
0
9
Enables/disables the use of an encoder’s Z-pulse to define the motor shaft’s zero position.
When enabled, a Z-pulse input resets parameter 0146
MECH
ANGLE
to zero to define the shaft’s
zero position. This function requires an encoder that provides Z-pulse signals.
0 =
DISABLE
– Z-pulse input is not present or ignored if present.
1 =
ENABLE
– A Z-pulse input resets parameter 0146
MECH
ANGLE
to zero.