![ABB OMD200 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/abb/omd200/omd200_installation-and-operating-instruction_2759042.webp)
42
AUTOM ATIC CONTROL U N ITS , OM D20 0 A N D 3 0 0
—
8 Technical data of the automatic
control units OMD200 / OMD300
Operating voltage
Main
voltagea
a)
208Vac - 480 Vac (±20%) + N
Phase
voltagea
a)
120Vac - 277 Vac (±20%)
Frequency
50 Hz, 60 Hz (±10%)
Voltage and frequency sensing precision
Voltage
5 %
Frequency
1 %
Relay utilization category
X21, X22
12 A, AC1, 250 V / 12 A, DC1, 24 V
X23
8 A, AC1, 250 V / 8 A, DC1, 24 V
X24
8 A, AC1, 250 V / 8 A, DC1, 24 V
X26, X27, X28
10 A, AC1, 250 V / 5 A, DC1, 24 V
Over voltage category
III, U
imp
6 kV
IP rating
IP40 for the front panel
Rango de temperaturas
– 20 to + 60 °C
Transportation and storage temperature
– 25 to + 80 °C
Humidity
with
condensation
5 % - 98 %
without
condensation
5 % - 90 %
a) OMD300: Rated voltage should be 380…415/220…240 Vac +/-20% in order that the dual power
source provides voltage supply.
Table 8.1
Technical data of OMD200 and OMD300