![ABB OMD200 Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/abb/omd200/omd200_installation-and-operating-instruction_2759040.webp)
40
AUTOM ATIC CONTROL U N ITS , OM D20 0 A N D 3 0 0
DIP switches S24
DIP-switch S24-1 to set neutral
S24-1
Position Neutral N
OFF
N used (default)
ON
N not in use
DIP- switch S24-2 to set phase system
S24-2
Position Generator
OFF
three-phase (default)
ON
single phase
DIP-switch S24-3 to set the generator in use
S24-3
Position Generator
OFF
not in use (default)
ON
in use
DIP-switch S24-4 to set the generator stop delay Gs
S24-4
Position Generator stop delay Gs
OFF
Gs = Switching delay Ts (default)
ON
Gs = 300 seconds