![ABB OMD200 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/abb/omd200/omd200_installation-and-operating-instruction_2759035.webp)
35
AUTOM ATIC CONTROL U N ITS , OM D20 0 A N D 3 0 0
AU TO M AT I C CO N T R O L U N I T S , O M D 2 0 0 -3 0 0
I key
Setting in manual mode the motorized change-over switch OTM_C to position I, when the I-switch will
be in the ON position and the II-switch will be in the OFF position.
II key
Setting in manual mode the motorized change-over switch OTM_C to position II, when the II-switch will
be in the ON position and the I-switch will be in the OFF position.
7.1.2 LEDs
Figure 7.3
LEDs on OMD200 and OMD300
Line 1 status (LN1)
A red LN 1 LED signals the status of the line LN 1. Line status and indication is explained in the Table 7.1.
Line 2 status (LN2)
A red LN 2 LED signals the status of the line LN 2. Line status and indication is explained in the Table 7.1.
I
II
Power
Auto
Alarm
LN 1
LN 2
K
A0029
3
Line Status
LED indication
Voltage OK
ON
No voltage
OFF
Overvoltage
Fast blinking (5 Hz, 50 % ON / 50 % OFF)
Undervoltage
Blinking (1 Hz, 50 % ON / 50 % OFF)
Invalid frequency
Blinking (1 Hz, 90 % ON / 10 % OFF)
Unbalance
Blinking (1Hz, 10 % ON / 90 % OFF)
Table 7.1
Line status indication