AUTOM ATIC CONTROL U N ITS , OM D20 0 A N D 3 0 0
Figure 7.5
Places of the DIP switches
If single phase is used, the neutral should be connected.
OMD
O
N
DIP
1
2
3
4
3
4
OMD200
OMD300
K
A0018
7
1 2 3 4 1 2 3 4
ON DIP
ON DIP
S23
S24
OMD
3
4
OMD100
1 2
ON
S23
7.2.2
DIP switches / parameter settings
Automatic control units OMD200 and OMD300 have total of eight (8) adjustable parameters. The
parameter settings are performed by the DIP switches and by the rotary switches.
Un
Rated voltage, setting by DIP switches S23-1...3
fn
Rated frequency, setting by DIP switch S23-4
N
Neutral in use, setting by DIP switch S24-1
Ph
Number of phases, setting by DIP switch S24-2
Gen
Generator in use, setting by DIP switch S24-3
Gs
Generator stop delay, setting by DIP switch S24-4
Ts
Switching delay, setting by Ts / Tbs rotary switch, see Section 7.2.1
Tbs
Back switching delay, setting by Ts / Tbs rotary switch, see Section 7.2.1
THR
Voltage threshold, setting by Lim rotary switch, see Section 7.2.1
S23
S24
Figure 7.6
DIP switches in OMD200 and OMD300, the positions are factory default settings
1 2 3 4
1 2 3 4
ON DIP
ON DIP
K
A00
357