36
AUTOM ATIC CONTROL U N ITS , OM D20 0 A N D 3 0 0
Switch in position I (I)
A red I LED is ON, when the motorized change-over switch OTM_C is in the I position (the I-switch is ON
and the II-switch is OFF), the LED is OFF otherwise. If transition from the O position to the I position
fails, the I LED will blink.
Switch in position II (II)
A red II LED is ON, when the motorized change-over switch OTM_C is in the II position (the II-switch is
ON and the I-switch is OFF), the LED is OFF otherwise. If transition from the O position to the II posi-
tion fails, the II LED will blink.
Alarm
A red Alarm LED signals an external alarm. Alarm status is explained in the Table 7.2. An active alarm is
set off by pushing the AUTO key.
Alarm Status
LED Indication
Handle attached
ON
Switching logic alarm
Blinking
No alarm
OFF
NOTE: When the handle is removed, the automatic control unit will stay in Manual Mode and the Alarm
LED will be OFF.
When the Alarm LED is ON or blinking, check the state of the motorized change-over
switch and repair the possible fault situation. An active alarm is set off by pushing the
AUTO key.
Table 7.2
Alarm status indication
Auto
A green Auto LED signals the automatic or the manual mode. When the OMD200 or OMD300 is in
automatic mode, the Auto LED is ON. When the device is in manual mode, the Auto LED is OFF. In
the test sequence, the Auto LED is blinking.
Power
A green Power LED signals the power status. When power is ON, the Power LED is ON. The OMD200or
OMD300 will remain in standby state at least one minute after power failure. A blinking Power LED
indicates standby mode.