NIBA-01 Installation and Start-up Guide
B-1
Appendix B – Technical Data
DDCS Link
Compatible Devices: All ABB Fieldbus Adapter modules,
ABB ACS 300, ACS 600 SingleDrive, ACS 600 MultiDrive,
ACS 600 MotionControl, ACF 600 Pump & Fan Drive, DCS 500
Size of the Link: 2 stations
Medium: Fibre optic cable
•
Construction: Plastic core, diameter 1 mm, plastic sheathing
•
Attenuation: 0.31 dB/m
•
Maximum Length between Stations: 10 m
•
Specifications:
Topology: Ring
Serial Communication Type: Asynchronous, half Duplex
Transfer Rate: 4 Mbit/s
Protocol: Distributed Drives Communication System (DDCS)
Connectors: Blue – receiver; grey – transmitter
Parameter
Minimum
Maximum
Unit
Storage Temperature
-55
+85
°C
Installation Temperature
-20
+70
°C
Short Term Tensile Force
50
N
Short Term Bend Radius
25
mm
Long Term Bend Radius
35
mm
Long Term Tensile Load
1
N
Flexing
1000
cycles