152 Technical data
AC input (supply) connection
Effect of AC power supply voltage on DC-bus voltage
100
100
150
200
250
300
350
125
150
175
200
225
250
AC supply voltage (RMS)
DC-bu
s voltage (V DC
)
Three-phase AC supply
Single-phase AC supply
1
Φ
3
Φ
Voltage (
U
1
)
200...240 V AC ±10%
200...240 V AC ±10%
Frequency
50...60 Hz ±5%
Network type
Grounded (TN, TT).
Corner grounded TN, and IT (ungrounded) systems not allowed.
Imbalance
Max.
±3% of nominal phase to
phase input voltage
Fundamental power
factor (cos phi
1
)
0.98 (at nominal load)
Terminals
Detachable screw terminal block for 0.20..6 mm
2
wire.
Short circuit current
protection
(UL 61800-5-1)
The drive is suitable for use on a circuit capable of delivering not more
than 5000 A rms symmetrical amperes, 240 V maximum, when
protected by fuses given in the fuse table on page
.