If one of the following mentioned axes are rotated one or more turns from its
calibration position before updating the revolution counter, the correct calibration
position will be lost due to non-integer gear ratio. This affects the following
manipulators:
Axis 6
Axis 4
Manipulator variant
Yes
No
IRB 1600
No
No
IRB 1600ID
If the synchronization marks seem to be wrong (even if the motor calibration data
is correct), try to rotate the axis one turn, update the revolution counter and check
the synchronization marks again (try both directions, if needed).
Step 2 - Updating the revolution counter with the FlexPendant
Use this procedure to update the revolution counter with the FlexPendant (IRC5).
Action
On the
ABB
menu, tap
Calibration
.
xx1500000942
1
Continues on next page
346
Product manual - IRB 1600/1660
3HAC026660-001 Revision: W
© Copyright 2006-2018 ABB. All rights reserved.
5 Calibration
5.3 Updating revolution counters
Continued