IM300 Intelligent Power Monitoring Instrument
71
999,999,999),unit is kvarh
Note 3:
when set at the bottom, you need to set the total branch
amount and the total amount of electricity.
Note 4:
When there is no multi-rate function, if you want to set the
base number of four-quadrant energy, you still need to write 10
registers at a time, and the settings of the sharp, peak, shouder, and
off-peak energy values are invalid.
Harmonic statistics (Harmonic distortion ratio/2-15th harmonic occupancy)
address table, supports read function of codes 03, 04
Address
Type
Data Definition
Register
40300
RO
Total harmonic distortion ratio
(
THD
)
of A-phase (Uab)
voltage
1
40301
RO
Total harmonic distortion ratio
(
THD
)
of B-phase (Ubc)
voltage
1
40302
RO
Total harmonic distortion ratio
(
THD
)
of C-phase (Uca)
voltage
1
40303
RO
Total harmonic distortion ratio of current Ia
1
40304
RO
Total harmonic distortion ratio of current Ib
1
40305
RO
Total harmonic distortion ratio of current Ic
1
40306
RO
Total harmonic distortion ratio of zero-sequence current
In
1
40308
RO
Odd harmonic distortion ratio of A-phase (Uab) voltage
1
40309
RO
Odd harmonic distortion ratio of B-phase (Ubc) voltage
1
40310
RO
Odd harmonic distortion ratio of C-phase (Uca) voltage
1
40311
RO
Odd harmonic distortion ratio of current Ia
1
40312
RO
Odd harmonic distortion ratio of current Ib
1
40313
RO
Odd harmonic distortion ratio of current Ic
1
40314
RO
Odd harmonic distortion ratio of zero-sequence current In
1
40315
RO
Even harmonic distortion ratio of A-phase (Uab) voltage
1
40316
RO
Even harmonic distortion ratio of B-phase (Ubc) voltage
1
40317
RO
Even harmonic distortion ratio of C-phase (Uca) voltage
1