IM300 Intelligent Power Monitoring Instrument
76
System parameter address table, supports read function of code 03,04 and
set function of code 06,10
Address
Type
Data Definition
Ranges
Defaults Regis
ter
Remarks
40510
RW
The limit value of
current
0~600000
meaning
0~6000A
6000A
2
Only
supports
writes
continuo
usly
40512
RW
The return value of
current
0~600000
meaning
0~6000A
5000A
2
40514
RW
Delay time
1~60000,Unit
:
ms
60000ms
1
40515
RW
Allow
0x0000(prohibit)
;
0xCC33H(allow)
0x0000
1
40516
RW
The limit value of
zero current
0~600000
meaning
0~6000A
0A
2
Only
supports
writes
continuo
usly
40518
RW
The return value of
zero current
0~600000
meaning
0~6000A
200A
2
40520
RW
Delay time
1~60000,Unit
:
ms
60000ms
1
40521
RW
Allow
0x0000(prohibit)
;
0xCC33H(allow)
0x0000
1
40522
RW
The limit value of
G
0~600000
meaning
0~6000A
6000A
2
Only
supports
writes
continuo
usly
40524
RW
The return value of
G
0~600000
meaning
0~6000A
5000A
2
40526
RW
G delay time
1~60000,Unit
:
ms
60000ms
1
40527
RW
G allow
0x0000(prohibit)
;
0xCC33H(allow)
0x0000
1
40528
RW
The limit value of
low voltage
0~420000
meaning
0~42000V
0V
2
Only
supports
writes
continuo
usly
40530
RW
The return value of
low voltage
0~420000
meaning
0~42000V
50V
2
40532
RW
Delay time
1~18000
meaning
0.1~1800s
1800s
1
40533
RW
Allow
0x0000(prohibit)
;
0xCC33H(allow)
0x0000
1
40534
RW
The limit value of
over voltage
0~420000
meaning
0~42000V
260V
2
Only
supports
writes
continuo
usly
40536
RW
The return value of
over voltage
0~420000
meaning
0~42000V
220V
2
40538
RW
Delay time
1~18000
meaning
0.1~1800s
1800s
1
40539
RW
Allow
0x0000(prohibit)
;
0xCC33H(allow)
0x0000
1
40540
RW
The limit value of
low voltage low
frequency
0~9999
meaning
0~99.99Hz
45.0Hz
2
Only
supports
Содержание IM300-I
Страница 1: ...IM300 Operational Manual ...
Страница 109: ...CNABB CNIIB IM300 201903 REV C ...