ABB IED 670 Скачать руководство пользователя страница 7

7

1MRK 500 080-UEN rev. -

The OPC server name, for IEC 61850-8-1 shall be: 
ABB.PCM.IEC61850_OPC_DA_Server.Instance[1].                                                  
This is set under: Communication structure/IEC61850/OPCserver/Properties.

Update the OPC server configuration under the communication structure as 
shown in

 

figure

 

7.

Connect to the IED with a crossed Ethernet cable, or straight if connected 
through a hub. You can ping the IEDs IP address in command mode to verify 
contact before starting to use the PCM 600 toolbox.

Configuration

Configure the IED with the CAP 531 Application configuration tool. The 
default password is abb. Right click on IED and select Application Configura-
tion.

The PCM 600 toolbox can be used to upload the ordered default configuration 
from the IED and then change it to suit the needs of the application, however 
the selected configuration will normally be sufficient for any application once 
the binary input/outputs and analog inputs have been defined in the signal 
matrix tool (described below).

If the configuration needs to be changed the existing configuration can be 
uploaded or the version in the CAP 531 template library used. The template 
library contains basic frameworks on which to build a complete configuration. 
In CAP 531 you can add worksheets and your own logic such as automatic 
switching logic etc. as required. It is advisable to always upload the IED 
options as a first step. This harmonizes available functions in the tool with the 
one in your IED. You can insert new worksheets under Edit, increase worksheet 
size or add functions on existing worksheets.

Insert your new functions from the function library into the selected locations. 
Click the inputs or outputs and type “v” to give variable names to a connection. 
Connect to the other end with the same signal name, alternatively draw the con-
nection with the connector tool. Outputs may go to several function blocks but 
inputs may only be connected to one so an OR gate might be required. Signals 
to other sheets shall preferably be drawn to the edge of the sheet where there is 
a red line. This ensures that signal cross-references will be shown at printout.

Open inputs are not allowed, connect them to FALSE (Off) or in some cases  to 
TRUE (On).

When you are ready, save and compile. Errors can be double-clicked to find the 
source of the error signal. This allows the user to quickly correct any errors.

Download the complete configuration with OnLine/Download or click the 
menu symbol. Do not interrupt during a download session. Downloading  
should take approximately 2 minutes. 

Once the download is completed testing can begin and the advantages of the 
debug tool become apparent. Activate the worksheet and select OnLine/Debug 
with the IED connected to the PC. This provides access to all signal status, red 
is active, blue is inactive and green is for floating numbers such as counters, 
phase selection etc. Test your IED to verify that the configuration is correct.

Note! The configuration connects signals to virtual IO which needs to be tied to 
the physical IO with the signal matrix tool described below. These connections 
must be made before the testing is started.

Note!

Signals from remote end via the LDCM 
communication card are configured with the 
signal matrix tool for connection to virtual 
analog input function blocks.

The Signal Matrix tool is also used to con-
figure what is shown by the 15 LED’s. Sig-
nals to the LED’s can be selected from 
virtual inputs or outputs so signals required 
to be shown must first be configured to the 
virtual IO blocks.

Содержание IED 670

Страница 1: ...atus bars ordering No 1MRK 000 020 BT are required A suitable test switch with contacts for example for a line protection IED such as REL 670 is selectable when ordering This allows commissioning and maintenance testing of the complete IED with many functions from one test handle Note The use of test switch RTXP24 NO contact 29 30 to perform software blocking has several advantages and is used dur...

Страница 2: ...n terminal or port on the rear side of the IED is numbered The numbers are stamped into the rear panel above each opening Viewed from the rear the lowest numbers are to the left and increase to the right All numbers begin with an X followed by two or three digits Analog inputs can be ordered with ring lug connectors as an alternative The analog inputs are dimensioned for conductor cross section ar...

Страница 3: ... used to navigate between different screens and data To change a setting select an item in the menu structure and change it using the up and down keys on the HMI After selecting parameter values move up through the menu system by repeatedly pushing the left arrow key until a dialog box appears where changes can be confirmed or cancelled The LEDs on the front panel of the IED are configured with th...

Страница 4: ...n PCM 600 The user can only LogOn or LogOff on the LHMI of the IED there are no users groups or functionalities that can be defined on the IED LHMI The display time out is set to 60 minutes at delivery At delivery the default user is the SuperUser No LogOn is required to operate the IED until a user has been created with the UMT See Application manual for more details The Help screen The help scre...

Страница 5: ... LANTIME which has been verified for Network Time Protocol NTP format The clock is connected to the station bus communication switch Other clocks can also be used but please check back if they were verified by ABB the same GPS satellite clock can synchronize an IED via a binay input B I with the disadvan tage of using copper cables over the whole substation The IED can also be synchronized from an...

Страница 6: ... Connectivity Packages for PCM 600 Prerequisites To operate with PCM 600 there must be at least one communication Con nectivity Package and one IED Connectivity Package installed and selected to be used with PCM 600 The IED Connectivity Packages are delivered with the IED s Start the PCM 600 from the desktop and build a new project For the new project your system structure with stations voltage le...

Страница 7: ...ts or outputs and type v to give variable names to a connection Connect to the other end with the same signal name alternatively draw the con nection with the connector tool Outputs may go to several function blocks but inputs may only be connected to one so an OR gate might be required Signals to other sheets shall preferably be drawn to the edge of the sheet where there is a red line This ensure...

Страница 8: ... appropriately chosen default IO arrangement but the tripping signals are connected to the physical IO supplied as basic supply Alarm signals and the like must be configured per application Analog signals can be connected to separate CT cores VT fuses and so on but different protection functions may also be connected to the same analog chan nels according to user preferences and the availability o...

Страница 9: ...order DR with 40 analog and 96 digi tal channels It has a default configuration and signals have been given names which will show up on the records The binary and also analog signals can by setting be made visible or hidden and to trigger a disturbance recording Select according to your preference for each of the 96 binary signals If you need to connect other signals or more signals or change name...

Страница 10: ...s document Each protection function has a function block with both analog and binary inputs and outputs The function blocks are described in detail in the Technical reference manual The analog inputs are connected by default to a pre process ing analog block in the configuration and a cross reference table is generated in the parameter setting tool PST which is part of the PCM 600 Ensure that the ...

Страница 11: ...y the IED This can be caused by a lost connection a clock failure or delayed signals caused by software handling In the latter case the signal will normally disappear automat ically Application problems The function does not trip or show up on the HMI Note First check that the function is set to ON and that it is not blocked or in test mode Verify the measurement by checking Test Function status I...

Страница 12: ...MRK 505 278 UEN Buyer s guide 1MRK 506 279 BEN Documents related to REC 670 Identity number Operator s manual 1MRK 511 188 UEN Installation and commissioning manual 1MRK 511 189 UEN Technical reference manual 1MRK 511 187 UEN Application manual 1MRK 511 190 UEN Buyer s guide 1MRK 511 191 BEN Documents related to RET 670 Identity number Operator s manual 1MRK 504 087 UEN Installation and commission...

Отзывы: