Commissioning
SA/S | 2CDC 505 056 D0208 91
3.2.3.1.4
Parameter window A: Logic
All settings for the
Logic
function are undertaken in this parameter window.
This parameter window is visible if
Enable function "logic"
has been enabled in
Parameter window
A: Function
, p. 71.
The
Logic
function provides up to two logic objects for each output, which can be logically connected via
the communication object
Switch
.
The logic is always re-calculated when an object value is received. First, the communication object
Logical
connection 1
is evaluated with communication object
Switch
. The result is then logically linked with
communication object
Logical connection 2
.
Explanations of the Logic function can be found in
Logic function
, p. 153. Please also observe the
Function diagram
, p. 147, where the priorities become evident.
Logical Connection 1
Options:
disable
enable
These parameters enable the communication object
Logical connection 1
.
•
enable
: The following parameters appear: