ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 71
3.2.3.1
Parameter window A: Function
In this parameter window you determine the response (reaction) of the output and can enable different
functions, which makes further parameter windows available.
Reaction of output A
Options:
Normally closed contact
Normally open contact
This parameter determines the reaction of the output as a normally open or normally closed contact.
•
Normally closed contact
: An ON telegram (1) opens the contact and an OFF telegram (0) closes it.
•
Normally open contact
: An ON telegram (1) closes the contact and an OFF telegram (0) opens it.
Enable time functions "delay, staircase lighting, flashing"
Options:
no
yes
•
no
: Parameter window
A: Time
is not enabled for output A.
•
yes
: Parameter window A:
Time
for output A, and communication object
Disable time function
, are
enabled.
Using this communication object, the Time function can be enabled (telegram with value 0) or disabled
(telegram with value 1) via the bus.
As long as the Time function is disabled, the output can be switched on and off only without delay via the
communication object
Switch
. The priorities as listed in
Function diagram
on p. 147 still remain valid.