ABB i-bus
KNX
Commissioning
80 2CDC 505 056 D0208 | SA/S
There are two types of warning:
1. The communication object
warning stair lighting
is set to the value 1 when the warning time starts, and
remains until it has elapsed. The communication object can be used, for example, to switch a warning
light.
2. Switching the output (briefly OFF and ON again).
Both options can be used together or separately. The time duration between the OFF and ON process is
about 1 second. If the warning time is not 0, the staircase lighting time is extended by the warning time.
Please note
When dealing with the warning time it is important to remember that the SA/S draws its switching
energy exclusively from the KNX. Furthermore, the SA/S collects enough energy before the first switch
to ensure that all outputs can safely go to the required position should the bus voltage fail. Under these
conditions, only a certain number of switching actions are possible per minute:
see
Technical data
, from p. 9.
Warning time in sec. [0...65,535] add
to duration of staircase lighting
Options:
0…45…65,535
This parameter is visible if you have set a warning before the staircase lighting time ends.
The warning time must be entered in seconds. The staircase lighting time is extended by the
warning time. The warning is triggered at the start of the warning time.
The warning time is not modified by “pumping up”.
Duration of staircase lighting can be
changed by object
“Staircase lighting time”
Options:
no
yes
•
yes
: A 2 byte
Duration of stair lighting
communication object is enabled. This can be used to change
the staircase lighting time via the bus. The value defines the staircase lighting time in seconds.
The staircase lighting function that has already started is completed first. A change is applied to the
staircase lighting time next time it is recalled.
•
no
: The staircase lighting time cannot be changed via the bus.
Please note
On bus voltage failure, the staircase lighting time changed via the bus is lost and must be reset.
Until a new value is set, the staircase lighting time set via ETS applies.