ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 139
No.
Function
Object name
Data type
Flags
27
Status Current-Threshold 1
Output A
EIS 1, 1 bit
DPT 1.002
C, T
This communication object is enabled if the
yes
option is selected for parameter
Enable current threshold value(s)
in the
A: Current Detection
parameter window.
The status of current threshold 1 is only sent when a change occurs.
The status value can be inverted.
Telegram value
1 = threshold value 1 plus threshold value 1 hysteresis is exceeded
0 = threshold value 1 minus threshold value 1 hysteresis is not exceeded
For further information see:
Threshold
function with current detection
, p. 142
28
Status Current-Threshold 2
Output A
EIS 1, 1 bit
DPT 1.002
C, T
This communication object is enabled if the
yes
option is selected for parameters
Enable current threshold value(s)
and
Enable threshold value 2
in the
A: Current Detection
parameter window.
The status of current threshold 1 is only sent when a change occurs.
The status value can be inverted.
Telegram value
1 = threshold value 2 plus threshold value 2 hysteresis is exceeded
0 = threshold value 2 minus threshold value 2 hysteresis is not exceeded
For further information see:
Threshold
function with current detection
, p. 142
29
Status Switch
Output A
EIS 1, 1 bit
DPT 1.001
C, R, T
This communication object is enabled if the options
only after changing
or
always
are selected for parameter
Status
response of switching state Object "Status Switch"
in parameter window A:
General
.
The communication object value directly indicates the current contact position of the switching relay.
The status value can be inverted.
Telegram value
1 = relay ON or OFF depending on the parameterization
0 = Relay OFF or ON depending on the parameterization