11.3.117 Fan coil settings for heating - Maximum speed level heating for eco mode
Options:
Setting option between 0 - 5
Specifies the maximum possible fan speed level when the system is switched to eco mode.
Pos: 31.7.145 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Kühlen @ 40\mod_1421746779519_15.docx @ 314204 @ 3 @ 1
11.3.118 Fan coil settings for cooling
Note
This parameter is only available if the "Device function" parameter is set on either
"Single device" or "Master device" and the "Control value type" parameter is set
on "Fan coil". In addition, the "Control function" parameter must be set on either
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
Pos: 31.7.146 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Kühlen — Lüfterstufe 1- 5 bis Stellgröße (0 - 255) Kühlen @ 40\mod_1421746840594_15.docx @ 314219 @ 3 @ 1
11.3.119 Fan coil settings for cooling - Speed level 1 to 5 up to control value (0 to 255) cooling
Options:
Setting option between 0 - 255
In this parameter, the control values of the controller are assigned to fan speed levels. This
assignment is used if the fan speed levels are transmitted together with the control values.
Note
■
These level settings should be adjusted to match the settings in the fan coil
actuator.
■
Setting the "Control value type" to "Fan coil" in the control parameters is only
useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the
control of only one fan coil actuator each for heating and cooling is supported.
■
The "Fan speed level 4 - 5 up to control value (0 - 255) cooling“ parameters
are available only when the "Number of fan speed levels" is set on "5 levels".
Pos: 31.7.147 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Kühlen — Lüfterstufenbegrenzung Kühlen bei Ecobetrieb @ 40\mod_1421746915412_15.docx @ 314234 @ 3 @ 1
11.3.120 Fan coil settings for cooling - Fan speed level limit cooling for eco mode
Options:
No
Yes
This parameter limits the fan speed level when the system is switched to eco mode.
Pos: 31.7.148 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Kühlen — max. Lüfterstufe Kühlen bei Ecobetrieb @ 40\mod_1421746987219_15.docx @ 314249 @ 3 @ 1
11.3.121 Fan coil settings for cooling - Maximum fan speed level cooling for eco mode
Options:
Setting option between 0 - 5
Specifies the maximum possible fan speed level when the system is switched to eco mode.
Pos: 31.7.150 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sommerkompensation @ 40\mod_1421748510803_15.docx @ 314264 @ 3 @ 1
11.3.122 Summer compensation
Note
This parameter is only available if the "Device function" parameter is set on either
"Single device" or "Master device".