FSM4000
ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
119
If the external data cannot be loaded in scenarios a) to d), the
program attempts to repair the defective data. The following
messages may be displayed:
• Warning 8a – (Update internal data) - for data flow
direction external → internal
• Warning 8b – (Update external data) - for data flow
direction internal → external
Both messages can be displayed simultaneously.
If this occurs, the following error is displayed:
• Error C – for the external FRAM, the FRAM thus must be
replaced
• Error 5 – for the internal FRAM, the transmitter starts
automatically with default values. In some instances, it
may be possible to eliminate this error by turning the
supply power off and on. If the error does not disappear,
the transmitter or the transmitter plug-in unit must be
replaced.
3. Check whether the language, display format, measuring
ranges, limit values and sensor data match the values listed
on the name plate of the sensor. If parameters are
subsequently changed, these are stored automatically in the
external FRAM.
4. The measuring system is ready for operation.
Returning devices
Use the original packaging or a secure transport container of an
appropriate type if you need to return the device for repair or
recalibration purposes.
Fill out the return form (see
on page 135) and
include this with the device.
In accordance with the EU Directive governing hazardous
materials, the owner of hazardous waste is responsible for its
disposal or must observe the following regulations for shipping
purposes:
All devices delivered to ABB must be free from any hazardous
materials (acids, alkalis, solvents, etc.).
Address for returns:
Please contact Customer Center Service according to page 6 for
nearest service location.