![ABB Foundation LD 810HSE Ex Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/abb/foundation-ld-810hse-ex/foundation-ld-810hse-ex_quick-installation-manual_2718010.webp)
10 Quick Installation Guide LD 810HSE Ex |
2PAA118721
complete units giving the material number stated on the device (marking,
type label).
– Only such auxiliary components may be used in potentially explosive
atmospheres that meet all requirements of European and national
directives and legislation.
– The environmental conditions specified in the manuals have to be followed
strictly.
– The Linking Device is not to be used in systems where cathodic systems
for corrosion protection are in place. Although special precautions such
as additional earthing bridges may allow the use in such systems, the
manufacturer has to be consulted in each case.
– The operator has to provide measures for protection against lightning.
– According to the local conditions and in compliance with the
environmental rules, the operator is responsible to visually inspect the
system and to remove dust settlements every 6 months.
– The company installing the device has to ensure that the transient
characteristic is limited to 40 % above the service voltage.
– Additional precautions have to be taken, if the presence of hydrosulphide,
ethylene oxide and/or carbon monoxide is to be expected. Those
substances are of a vary low ignition energy.
– Icing is not permitted.
Make sure that the sum of power supply voltage and fieldbus
supply voltage does not exceed 60 V DC.
Содержание Foundation LD 810HSE Ex
Страница 1: ...Quick Installation Guide FOUNDATION Fieldbus Linking Device LD 810HSE Ex Version 1 0 ...
Страница 19: ...2PAA118721 Quick Installation Guide LD 810HSE Ex 19 The receive RX and transmit TX signals must be crosslinked ...
Страница 35: ...2PAA118721 Quick Installation Guide LD 810HSE Ex 35 This page is intentionally left blank ...
Страница 36: ...www abb com 800xA www abb com controlsystems Contact us Copyright 2018 ABB All rights reserved ...