FEP630, FEH630
ELECTROMAGNETIC FLOWMETER | CI/FEP630/FEH630-EN REV. D
63
Exiting the setup
For some menu items, values must be entered. If you don't want
to change the parameter, you can exit the menu as described
below.
1. Pressing
(Next) repeatedly moves the cursor to the right.
Once the cursor reaches the end position, ‘Cancel’ is
displayed in the lower right of the screen.
2.
terminates editing and exits the menu item. Use
to
return to the start.
Note
The LCD display automatically returns to the process display
three minutes after the last button has been actuated.
Brief overview of configurations
Configuration of digital output 41 / 42 as pulse output for
forward flow and digital output 51 / 52 as pulse output for
reverse flow.
Menu / parameter
Parameter setting
Input/Output / Dig.Out 41/42 / …
Mode
Ň
Pulse
Outp. Flow Direction
Ň
Forward
Input/Output / ...Setup Pulse Output
Output Value Pulse
Ň
Pulse
Volume
Flow
Pulses per Unit
Ň
Setting in accordance with
requirement
Pulse Width
Ň
Setting in accordance with
requirement
Input/Output / Dig.Out 51/52
Mode
Ň
Follow
DO
41/42
Extended diagnostic functions
Overview
Note
• The extended diagnostic functions are only available on the
ProcessMaster FEP630 and HygienicMaster FEH630 if the
‘Extended diagnostic functions’ software package has been
ordered (see table) .
• The ‘Partial Filling Detector’ function is
not
available for
HygienicMaster FEH630.
• To facilitate initial commissioning, the individual diagnosis
options of the extended diagnostic functions are deactivated
(factory default).
• Each diagnostic function (e.g. Gas Bubble Detector or
Electrode Deposit Detector) can be individually activated.
Once activated, the diagnostic function must be calibrated
according to the conditions on site and the limit values must
be set.
Diagnostic Functions
Standard
Empty pipe detection (EPD)
Partial filling detection (TFE)
Noise / grounding check
Fingerprint
verification
Service
interval
Transmitter
temperature
Software package ‘Extended
diagnostic functions’ (optional)
Coil/sensor temperature
Coil inductance
Gas
bubble
detection
Conductivity
monitoring
Electrode impedance / Leakage
Monitoring
Filling function (optional)
Filling function