Modbus-RTU Example Connection A-5
MN448
Register
Parameter
Description
Format
Min
Max
Data format / scaling
131
1103
Control mode
U16
0
6
0: Terminal Control
1: Keypad forward only
2: Keypad forward and
reverse
3: Modbus control mode
4: Modbus control with ramp
control
5: PID control
6: PID control with analog
speed sum
7: CAN Open
132
1202
Preset Speed 1
U16
-2008
2008
Internal value (3000 = 50.0Hz)
133
1203
Preset Speed 2
U16
-2008
2008
Internal value (3000 = 50.0Hz)
134
1204
Preset Speed 3
U16
-2008
2008
Internal value (3000 = 50.0Hz)
135
1205
Preset Speed 4
U16
-2008
2008
Internal value (3000 = 50.0Hz)
136
1300
Analog input
format
U16
0
7
0: 0…10V
1: b 0…10V
2: 0…20mA
3: t 4…20mA
4: r4…20mA
5: t 20…4mA
6: r 20…4mA
7: 10…0V
137
1301
Analog iput offset
U16
-5000
5000
1dp,e.g. 300=30.0%
138
1302
Analog Input /
Slave Scaling
U16
0
20000
1000 = 100.0%
139
1304
Analog Input 2
Format
U16
0
6
0: 0…10V
1: b 0…10V
2: 0…20mA
3: t 4…20mA
4: r4…20mA
5: t 20…4mA
6: Ptc-th
140
1401
Relay Output
Function
U16
0
9
See user guide for function
details
141
1501
Analog Output
Function
U16
0
10
See user guide for function
details
142
1602
Parameter lock
U16
0
1
0: Unlocked
1: Locked
143
1603
Access code
definition
U16
0
9999
Содержание EC Titanium Series
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......