Technical Data 12-1
MN448
Chapter 12
Technical Data
This chapter contains the technical specifications of the drive, the ratings, sizes and technical requirements.
12.1 Environmental
Motor Enclosure Rating
TEFC/IP54 Motor with UL
Drive Enclosure Rating
Type 12/IP55 Drive
Operational ambient temperature ranges:
-10 … 50°C (frost and condensation free)
Storage ambient temperature range:
-40 … 60°C
Maximum Altitude:
2000 meters, de-rate above 1000m: 1% / 100m
Maximum Humidity:
95%, non-condensing
Vibration (Operating)
1 G Peak at 20 Hz
Vibration (Non-Operating)
0.2G Peak at 20 to 50Hz
12.2 Input Power Electrical Data
Supply Voltage Range
110 Volt Units – 110 – 115 Volt +10% / -10%
230 Volt Units – 200 – 240 Volt +10% / -10%
400 Volt Units – 380 – 480 Volt +10% / -10%
Supply Frequency
48 – 62Hz
Inrush Current
< rated input current
Power Up Cycles
>120x /hr, evenly spaced
Single Phase Operation
Three phase drives can be operated from a single phase supply with 50%
derating of the maximum output current
Earth Leakage
When operating from a balanced three phase supply with the permissible
supply voltage range, touch current according to IEC61800-5-1 does not
exceed 3.5mA.
12.3 Motor Control Electrical
Output Frequency Range
0 to 500Hz in 0.1 Hz steps
Max Output Frequency = Max Switching Frequency / 16.
Output Voltage Range
0 to Supply Voltage
Speed Regulation
Open Loop < 2% motor rated speed
Torque Control
0 – 175% of rated torque, + / -5% accuracy, Response time <10ms
Effective Switching Frequency
4 – 32kHz
Acceleration Time
0 – 600 seconds, 0.01s resolution
Deceleration Time
Two deceleration ramps
0 – 600 seconds, 0.01s resolution
12.4 Motor Control Performance
V/F Mode
Speed Regulation:
+ / - 20% of motor slip with slip compensation enabled
Vector Mode
Static Speed Accuracy:
+ / - 0.033%
Speed Regulation
0 – 100% Load Range: + / - 1%
Torque Response:
1- 8ms
Torque Linearity
(10 – 90% of motor rated speed, 20 – 100% load torque
range): + / - 5%
Содержание EC Titanium Series
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......