5-5 Control Pad Wiring and Keypad Interface
MN448
5.5 Motor Thermistor Connection
When an externally mounted motor thermistor is to be used, connect as follows:
Control Terminal Strip
1
2
3
4
Additional Information
• Compatible Thermistor: PTC Type
• Trip Level: >=2.5 kΩ
• Reset Level: =<1.9 kΩ
• The thermistor input is monitored at all times and the
drive may trip even if it is disabled.
• Use suitable settings of parameter 1103 Command
Source and 9902 Digital Input Function Select which have
Input 3 function as External Trip, (1103 = 0, 9902 = 3)
Refer to Chapter 12 for further information.
• Set 1304 Analog Input 2 Format =
Ptc-th
. If this
setting is not used, the drive will display
E-trP
only
if the thermistor exceeds the threshold level during
operation.
5.6 Internal Thermal Overload Protection
The drive has an in-built motor thermal overload function; this is in the form of an
It-trP
trip after delivering >100% of
the value set in 9906 Motor Rated Amps for a sustained period of time (150% for 60 seconds).
Содержание EC Titanium Series
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......