9-2 Control Modes
MN448
9902 Digital input 1
Digital Input 2
Digital Input 3 (An in 2)
Digital input 4 (An in 1)
Comments
9
Open: Fwd. Stop
Closed: Fwd. Run
Open: Reverse stop
Closed: Reverse run
Preset speed select 0
Preset speed select 1
Closing digital inputs 1 and
2 together carries out a
fast stop
10
Normally Open
(NO)
Momentary close
to run
Normally Closed (NC)
Momentary open to stop
Open: Analog input 1
Closed: Preset speed 1
Analog input 1
11
Normally Open
(NO)
Momentary close
to Fwd
Normally Closed (NC)
Momentary open to stop
Normally Open (NO)
Momentary close to Rev
Analog input 1
Closing digital inputs 1 and
3 together carries out a
fast stop
12
Open: Stop
(disable)
Closed: Run
(enable)
Close to Run
Open activates fast stop
Open: Analog input 1
Closed: Preset speed 1
Analog input 1
13
Normally Open
(NO)
Momentary close
to Fwd
Normally Closed (NC)
Momentary open to stop
Normally Open (NO)
Momentary close to Rev
Open: Keypad Speed Ref
Closed: Preset speed 1
Closing digital inputs 1 and
3 together carries out a
fast stop
14
1
Open: Stop
(disable)
Closed: Run
(enable)
Preset speed select 0
External trip/thermistor input:
Open: Trip, Closed: Run
Preset speed select 1
Preset speed 1 .. 4
selected as defined in this
table
Note:
1. 1. When PTC motor thermistor is used,
1304
must set to "PTC-th" mode. Otherwise digital input 3 will be used as external trip input (digital
level sensitive). When
1304
is set to "PTC-th", drive will display code "F-Ptc" if thermistor value is larger than 2.5kohm. The trip can only be
reset if the thermistor value drops below 1.9kohm. Thermistor must be connected between terminal 1 (24V DC) and terminal 4 (2nd analog
input). If
1304
is set t other value, the input will be used as external trip trigger input and drive will display code "E-trp" instead if the input is
open.
"E-trp" only happens when drive is enabled (running), however thermistor trip can happen at any time.
Preset Speed selection table for
9902
= 2, 8, 9 or 14:
Preset Speed Select 0
Preset Speed Select 1
Preset Speed
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
Содержание EC Titanium Series
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......