ACH550-UH User’s Manual
105
3405
OUTPUT1 DSP UNIT
-128…127
1
4
Selects the units used with the first display parameter.
• Enter positive values in parameter 3405 for a numeric display.
• Enter negative values in parameter 3405 for a bar-graph display.
3406
OUTPUT1 MIN
Depends on selection
-
0.0%
Sets the minimum value displayed for the first display parameter.
3407
OUTPUT1 MAX
Depends on selection
-
1000.0%
Sets the maximum value displayed for the first display parameter.
3408
SIGNAL 2 PARAM
100…199
1
104
Selects the second parameter (by number) displayed on the control panel. See parameter 3401.
3409
SIGNAL 2 MIN
Depends on selection
-
4.3 A
Defines the minimum expected value for the second display parameter. See parameter 3402.
3410
SIGNAL 2 MAX
Depends on selection
-
9.2 A
Defines the maximum expected value for the second display parameter. See parameter 3403.
3411
OUTPUT 2 DSP FORM
0…8
1
5
Defines the decimal point location for the second display parameter. See parameter 3404.
3412
OUTPUT 2 DSP UNIT
-128…127
1
1
Selects the units used with the second display parameter. See parameter 3405.
3413
OUTPUT 2 MIN
Depends on selection
-
0.0 A
Sets the minimum value displayed for the second display parameter. See parameter 3406.
3414
OUTPUT 2 MAX
Depends on selection
-
9.2 A
Sets the maximum value displayed for the second display parameter. See parameter 3407.
3415
SIGNAL 3 PARAM
100…199
1
120
Selects the third parameter (by number) displayed on the control panel. See parameter 3401.
3416
SIGNAL 3 MIN
Depends on selection
0.0%
Defines the minimum expected value for the third display parameter. See parameter 3402.
3417
SIGNAL 3 MAX
Depends on selection
100.0%
Defines the maximum expected value for the third display parameter. See parameter 3403.
3418
OUTPUT 3 DSP FORM
0…8
1
5
Defines the decimal point location for the third display parameter. See parameter 3404.
3419
OUTPUT 3 DSP UNIT
-128…127
1
11
Selects the units used with the third display parameter. See parameter 3405.
3420
OUTPUT 3 MIN
Depends on selection
0.0 mA
Sets the minimum value displayed for the third display parameter. See parameter 3406.
Group 34: Panel Display Process Variables
Code Description Range
Resolution
Default
S
0 =
NOT
SEL
8 = kh
16 = °F
24 = GPM
32 = kHz
40 = m
3
/m
48 = gal/m
56 = FPS
1 = A
9 = °C
17 = hp
25 = PSI
33 = Ohm
41 = kg/s
49 = gal/h
57 = ft/s
2 = V
10 = lb ft
18 = MWh
26 = CFM
34 = ppm
42 = kg/m
50 = ft
3
/s
58 = inH
2
O
3 = Hz
11 = mA
19 = m/s
27 = ft
35 = pps
43 = kg/h
51 = ft
3
/m
59 = in wg
4 = %
12 = mV
20 = m
3
/h
28 = MGD
36 = l/s
44 = mbar
52 = ft
3
/h
60 = ft wg
5 = s
13 = kW
21 = dm
3
/s
29 = inHg
37 = l/min
45 = Pa
53 = lb/s
61 = lbsi
6 = h
14 = W
22 = bar
30 = FPM
38 = l/h
46 = GPS
54 = lb/m
62 = ms
7 = rpm
15 = kWh
23 = kPa
31 = kb/s
39 = m
3
/s
47 = gal/s
55 = lb/h
63 = Mrev
117 = %ref
119 = %dev
121 = % SP
123 = Iout
125 = Fout
127 = Vdc
118 = %act
120 = % LD
122 = %FBK 124 = Vout
126 = Tout