238
ACH550-UH User’s Manual
Technical Data
Analog Cables
Recommendations for analog signal runs:
•
Use double shielded, twisted pair cable.
•
Use one individually shielded pair for each signal.
•
Do not use a common return for different analog signals.
Digital Cables
Recommendations for digital signal runs:
•
A double shielded cable is the best alternative, but single-shielded, twisted, multi-
pair cable is also usable.
Control Panel Cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch
ethernet cable.
Drive’s Control Connection Terminals
The following table provides specifications for the drive’s control terminals
Control Terminal Descriptions
The following full-page diagram provides a general description of the control
terminals on the drive. For specific application details, see the "Application Macros"
on page 35.
Note!
Terminals 3, 6, and 9 are at the same potential.
Note!
For safety reasons the fault relay signals a “fault” when the ACH550 is
powered down.
Frame Size
Control
Maximum Wire Size
Torque
mm
2
AWG
Nm
lb-ft
All
1.5
16
0.4
0.3