DCS880 control panel

Refer to ACS-AP-x assistant control panels user’s manual (

3AUA0000085685

) for detailed information.

BE_PAN_002_DCS880_overview_a.ai

Status LED:

• Green for normal operation

• Flashing green for alarms

• Red for faults

 

Soft key 1

Local reference up

Loc/Rem – Changes between local and 

remote control of the drive.

Stop – Stops the drive in local control 

from DCS Control Panel and when 

the Start-up Assistant is used.

Soft key 2 

Local reference down

Help – Displays context sensitive 

information when the button is pressed. 

Start – Starts the drive in local control 

from DCS Control Panel and when the 

Start-up assistant is used.

USB connection to composer PC Tool

Direction of speed

Actual control location

Local reference - change by arrow 

buttons (up/down)

Signals selected by edit Home View

(option menue)

 

DCS880 Set up control panel assistant

General display features

Following modes are available in the MAIN MENU:

1.

Basic assistant (menue / assistant)

a.

Data and time

2.

DCS880 assistant (menue / assistant)

a.

Name plate data

b.

Autotuning field current controller

c.

Autotuning armature current controller

d.

First 

time 

motor turning

e.

Speed feedback assistant
(Tacho fine tuning not available)

f.

Autotuning speed controller

g.

Field weakening assistant (only used when

 

maximum speed is higher than base speed)

h  Make a back up

3. Parameter backup (menue / parameter backup)

Parameters entered by assistant

99.07  M1 used field exciter type
99.10  Nominal mains voltage
99.11  M1 nominal current 
99.12  M1 nominal voltage
99.13  M1 nominal field current
99.14  M1 nominal (base) speed
30.11  M1 minimum speed
30.12  M1 maximum speed
30.19  Minimum torque 1
30.20  Maximum torque 1
30.35  M1 current limit bridge 1
30.34  M1 current limit bridge 2
31.30  M1 overspeed trip margin
31.44  Armature overcurrent level
94.23  OnBoard encoder pulses/revolution
94.24  OnBoard encoder type
94.25  OnBoard encoder speed calculation mode
94.07  M1 tacho type
94.08  M1 tacho voltage at 1000 rmp
90.41  M1 feedback selection
23.12  Acceleration time 1
23.13  Deceleration time 1
31.58  M1 field current low level
28.17  M1 EMF/field control mode

DCS880 commissioning is supported by assistants available in the control panel.  
The digital inputs can be tested by 10.04 DI force data. 
The analog inputs can be tested by 12.11 AI1 actual value and AI1 scaled value 12.12 (AI2 = 12.21 and 12.22).
Start commisioning always with date and time setting, follow the assistants and close with parameter  
backup in the control panel.

Содержание DCS880 series

Страница 1: ...DC drives ABB industrial drives DCS880 Quick guide...

Страница 2: ...15 Terminal locations of the converter 16 Control circuit terminal layout 17 Notes For North American Installations 18 DCS880 control panel 20 Drive composer PC tool 21 Parameter groups 22 Control loo...

Страница 3: ...normas comunes as como a su funcionamiento Esto significa para nuestros clientes Visiten el portal de convertidores de ABB www abb com drivesservices Country Local ABB Service Town Service Phone No Ar...

Страница 4: ...atud hendage lahti k ik pingeallikad sealhulgas v lised pingeallikad ja mootor v i generaator Veenduge et taas henduse tekkimine ei ole v imalik lukustage ja t histage Oodake 5 minutit kuni kondensaat...

Страница 5: ...pra estas instru es Se ignorar as mesmas podem ocorrer ferimentos ou morte ou danos no equipamento Consulte os manuais de produto para mais instru es e informa es AVISO Seguran a na instala o e manute...

Страница 6: ...dule 3AFE68615500 x x FDNA 01 DeviceNet adapter module 3AFE68573360 x FECA 01 EtherCAT adapter module 3AUA0000068940 x x FENA 11 21 Ethernet adapter module 3AUA0000093568 x FEPL 02 Ethernet POWERLINK...

Страница 7: ...ng in glass plastic or metal industry DCS880 DC drive Our DCS880 industrial drives are customized to meet the precise needs of industries such as oil and gas mining metals cement non motoric material...

Страница 8: ...8 225 250 18 270 300 18 H3 290 320 25 460 x 270 x 317 18 11 x 10 63 x 12 48 315 350 25 405 450 25 470 520 25 H4 590 650 38 645 x 270 x 352 25 39 x 10 63 x 13 86 610 680 30 740 820 30 900 1000 30 H5 11...

Страница 9: ...for frame details Cabinet installation The required distance between parallel units is five millimetres 0 2 in in installations without the front cover The cooling air entering the unit must not exce...

Страница 10: ...8 Revision code f 0 1st generation Field exciter configuration 0S163 S164 H1 H4 without OnBoard field exciter H5 and H6 with internal field exciter supply external H5 and H6 25 A Rebuild kit 16 A 25 A...

Страница 11: ...al information about DCS880 STO function and how to handle Service manual 3ADW000488 for maintenance and repair of the converters Applications DCS880 DC Drive can include application software e g magn...

Страница 12: ...ains filter Line reactor Converter Converter An isolating transformer with an earthed screen and earthed iron core renders mains filter and line reactor superfluous Operation at public low voltage net...

Страница 13: ...lassif_a ai I DC 100 A I DC 100 A I DC 100 A Supply transformer for a residential area rating normally 1 2 MVA Earthed 400 V network with neutral conductor 3 400 A Converter transformer Case reference...

Страница 14: ...time delay In case of 21 03 Emergency stop mode Ramp stop the timer relay K15 must be set longer than 23 23 Emergency stop time For 21 03 Emergency stop mode Coast stop the drive opens the mains conta...

Страница 15: ...4 5 6 2 XAO 1 2 3 4 IACT 5 XD24 1 2 3 4 5 8 9 OnBoard tacho feedback OnBoard Encoder Feedback U1 V1 W1 D1 C1 1 2 XAUX X99 3 4 K1 L1 L2 L3 F1 1 5 2 6 Power supply F5 1 2 1 max 270 V 7 EGND 24 V 5 V 8...

Страница 16: ...1 1 x 4 1 x 10 1 x M6 6 DCS880 S0x 0050 xx 50 1 x 10 41 1 x 6 1 x 10 1 x M6 6 DCS880 S0x 0075 xx 75 1 x 25 61 1 x 25 1 x 16 1 x M6 6 DCS880 S0x 0100 xx 100 1 x 25 82 1 x 25 1 x 16 1 x M6 6 DCS880 S0x...

Страница 17: ...A 2 A Channel A function depending on J4A 3 B Channel B function depending on J4B 4 B Channel B function depending on J4B 5 Z Channel Z function depending on J4C 6 Z Channel Z function depending on J4...

Страница 18: ...er to command the drive to perform a DB stop one or more of these parameters must be set to DynBraking Most users will want the drive to ramp stop when OnOff or a run command StartStop Jog1 Jog2 etc i...

Страница 19: ...and time press SELECT Second step DCS880 SETUP for name plate data and autotunings press SELECT Step 1 Check converter for damage Contact ABB Technical Support if damage is found In North America cal...

Страница 20: ...current controller d First time motor turning e Speed feedback assistant Tacho fine tuning not available f Autotuning speed controller g Field weakening assistant only used when maximum speed is highe...

Страница 21: ...ode J428 DPI H01 System info menue With the menue system info the drive name and drive internal clock can be set It is important for backup function and makes datalogger handling very easy For basic c...

Страница 22: ...gs 49 Panel port communication Local time out 50 Fieldbus adapter FBA Fieldbus communication configuration 51 FBA A settings Fieldbus adapter A 52 FBA A data in Data sent to fieldbus adapter A to the...

Страница 23: ...tion Safety instructions drives commisioning Ensure sufficient cooling Do not fasten the drive by riveting or welding Operation Warning Before adjusting the drive and putting it into service make sure...

Страница 24: ...mains voltage 99 12 M1 nominal voltage 99 14 M1 nominal base speed Aux codes Cause and what to do 00030004 Autotuning timeout Run command 06 09 b03 Used main control word was not set in time or is mis...

Страница 25: ...gree IEC 60664 1 IEC 60439 1 2 Overvoltage category IEC 60664 1 all inputs III Protective class Site elevation IEC 61800 5 1 I 1000 m above M S L 100 without current reduction 1000 m above M S L with...

Страница 26: ...speed 6 22 31 Speed reference 22 07 22 12 22 14 19 12 19 14 6 15 6 24 6 17 Encoder MCW COM NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3 4...

Страница 27: ...6 15 6 24 6 17 Encoder MCW COM NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3 4 IACT 5 8 9 NC COM NO NC COM NO NC COM NO 12 11 22 21 23 13 X...

Страница 28: ...e 22 07 22 12 22 14 19 12 19 14 6 15 6 24 6 17 Encoder MCW COM NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3 4 IACT 5 8 9 NC COM NO NC COM N...

Страница 29: ...NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3 4 IACT 5 8 9 NC COM NO NC COM NO NC COM NO 12 11 22 21 23 13 XRO2 32 31 33 XRO3 AI1 J1 AI2 J2...

Страница 30: ...nt speed 6 22 31 Speed reference 22 07 22 12 22 14 19 12 19 14 6 15 6 24 6 17 Encoder MCW COM NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3...

Страница 31: ...22 07 22 12 22 14 19 12 19 14 6 15 6 24 6 17 Encoder MCW COM NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3 4 IACT 5 8 9 NC COM NO NC COM NO...

Страница 32: ...6 22 31 Speed reference 22 07 22 12 22 14 19 12 19 14 6 15 6 24 6 17 Encoder MCW COM NO COM NO XSMC 3 4 2 1 10V 10V AGND AI1 AI2 AI2 AI1 AO2 AGND AGND AO1 AI3 AI3 XAI 1 2 3 4 5 6 7 XAO 1 2 3 4 IACT 5...

Страница 33: ...04 Emergency stop source 20 05 Bit 0 Off1 control Bit 1 Off2 control Bit 2 Off3 control Bit 3 Run Bit 4 Ramp out zero Bit 5 Ramp halt Bit 6 Ramp in zero Bit 7 Reset Bit 8 Inching 1 Bit 9 Inching 2 Bit...

Страница 34: ...t3 Run Bit4 Ramp out zero Bit5 Ramp halt Bit6 Ramp in zero Bit7 Reset Bit8 Inching 1 Bit9 Inching 2 Bit10 Remote command Bit11 reserved Bit12 15 Main control 06 01 4 Application 3 EFB 2 FBA B 0 None 1...

Страница 35: ...001 1000 DIO status 0b0000 RO1 source Ready run RO2 source Not energized RO3 source Tripped 1 AI AO AI1 actual value 1 093 AI2 actual value 0 006 AI3 actual value 0 001 AO1 actual value 0 000 AO2 actu...

Страница 36: ...36 ABB industrial drives DCS880 Quick guide 3ADW000480R0201 36 ABB industrial drives DCS880 Quick guide Declarations...

Страница 37: ...37 DC drives 37 DC drives Appendix...

Страница 38: ...12 pulse up to 20 000 A 1 500 V In accordance to usual standards Individually factory load tested Detailed documentation Precise power control in industrial heating applications Two or three phase dev...

Страница 39: ...39 DC drives 39 DC drives Appendix...

Страница 40: ...www abb com dc drives www abb com drivespartners Copyright 2019 ABB All rights reserved Specifications subject to change without notice 3ADW000480R0201 REV B EN 09 01 2019...

Отзывы: