17
D C D r i v e s
17
D C D r i v e s
en
gl
is
h
—
Control circuit terminal layout
Relay driver
2k
+24 V
DC
+3.3 V
DC
max. +24 V
DC
DO
DI
100n
DIOGND
2k
+3.3 V
DC
max. +24 V
DC
DI1 ... DI5 and DIL
DI
100n
DICOM
2k
+3.3 V
DC
max. +24 V
DC
DI6
DI
100n
DIOGND
XAI
Reference voltage and analog inputs
1
+VREF
+10 V
DC
2
-VREF
-10 V
DC
3
AGND
Common ground (connected to frame)
4
AI1+
±10 V or 0 (4) ... 20 mA depending on J1
5
AI1-
6
AI2+
±10 V or 0 (4) ... 20 mA depending on J2
7
AI2-
8
AI3+
±10 V
9
AI3-
J1
J1
AI1 current / voltage selection jumper
J2
J2
AI2 current / voltage selection jumper
XAO
Analog outputs
1
AO1
±10 V or 0 (4) ... 20 mA depending on J5
2
AGND
Common ground (connected to frame)
3
AO2
±10 V
4
AGND
Common ground (connected to frame)
5
IACT
Connection point for a scope (H1 ... H6 only)
J5
J5
AO1 current / voltage selection switch
XD2D Drive-to-drive link
1
B
Drive-to-drive link
2
A
(master-follower or embedded fieldbus)
3
BGND
Isolated ground 2
J3
J3
Drive-to-drive link termination switch
XRO1, XRO2, XRO3 Relay outputs
11 NC
12
COM
250 V
AC
/ 30 V
DC
13
NO
2 A
21 NC
22
COM
250 V
AC
/ 30 V
DC
23
NO
2 A
31 NC
32
COM
250 V
AC
/ 30 V
DC
33
NO
2 A
XD24 Digital interlock
1
DIL
Digital interlock, ground: DICOM
2
+24VD
+24 V
DC
, 200 mA, ground : DIOGND
3
DICOM
Isolated digital input ground for DI1 ... DI5 and DIL
4
+24VD
+24 V
DC
, 200 mA, ground : DIOGND
5
DIOGND
Isolated digital input / output ground for DI6, DIO1, DIO2
J6
J6
Digital ground selection switch (DIOGND and DICOM)
XDIO
Digital inputs / outputs
1
DIO1
2
DIO2
XDI
Digital inputs
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
XENC Encoder
1
A+
Channel A+ function depending on J4A
2
A-
Channel A- function depending on J4A
3
B+
Channel B+ function depending on J4B
4
B-
Channel B- function depending on J4B
5
Z+
Channel Z+ function depending on J4C
6
Z-
Channel Z- function depending on J4C
7
EGND
Common ground (connected to frame)
8
+VENC
Encoder supply 5 V
DC
or 24 V
DC
depending on J4D, 250 mA
J4A
J4A
Differential or single ended (10 k pull up)
J4B
J4B
selection jumpers
J4C
J4C
J4D
J4D
Encoder supply 5 V
DC
or 24 V
DC
selection jumper
J7A
J7A
Not in use for DCS880
J7B J7B
XTAC Analog tacho
1
±8 … 270 V
DC
2
AITACH-
XSMC Mains contactor
1
MCCOM
250 V
AC
/ 30 V
DC
Fixed output for the mains
2
MCNO
2 A contactor
3
STOCOM
250 V
AC
/ 30 V
DC
Fixed output for safe torque
4
STONO
2 A
off (STO) zero current monitor
XSTO Safe torque off (STO)
1
OUT1
24 V
DC
for STO circuit
2
SGND
Common ground (connected to frame)
3
IN1
Both circuits must be closed for drive to start
4
IN2
Open circuits block the firing pulses
X12
Safety functions module connection
X13
Control panel connection
X205
Memory unit connection
For H7 and H8 see SDCS-OPL-H01.
SA_880_005_DCS_d.ai
DCS880
Safety
relais
Recommended wire size - Tightening torques
Control cables:
Wire sizes:
Tightening torques:
0.5 … 2.5 mm2 (24 … 12 AWG)
0.5 Nm (5 lbf·in)
for both, stranded and
solid wiring
Auxiliary power supply (X99 located on PIN-H01)
Wire sizes:
Tightening torques:
0.25 … 1.5 mm2 (stranded)
0.2 … 1.0 mm² (solid)
0.5 Nm (5 lbf·in)
for both, stranded and
solid wiring
External 24 V
DC
used
XD24 Digital interlock
1
DIL
2
+24VD
3
DICOM
4
+24VD
5
DIOGND
J6 J6
XDIO Digital input / outputs
1
DIO1
2
DIO2
XDI
Digital inputs
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
Power
supply
PLC
0 V
DC
24 V
DC
SA_880_010_DCT-PLC_a.ai
default
default
J4
A B C
J4
D
Encoder
supply
10 kΩ
24 V
5 V
120 Ω
pull up