16
A B B i n dustr i A l dr i v e s
D C S 8 8 0 Q u i C k g u i D e - 3 A D W 0 0 0 4 8 0 R 0 2 01
16
A B B i n dustr i A l dr i v e s
D C S 8 8 0 Q u i C k g u i D e
—
Terminal locations of the converter
Ch. A+ Ch. A- Ch. B+ Ch. B- Ch. Z+ Ch. Z-
GND
+5V or +24V
DI1 DI2 DI3 DI4 DI5 DI6
COM
NO
COM
NO
OUT1 SGND
IN1 IN2
DIL
+24VD DICOM +24VD
DIOGND
DO1
DO2
1 2 3 4 5 6 7 8 9
1 2 3 4 5
+10V
-10V
AGND
AI1-
AI1+
AI2-
AI2+
AI3-
AI3+
AO1 +10V -10V GND
24V 0V
GNDB CANL CANH
GNDB CANL CANH
AO1
11 12 13
NC
COM
NO
21 22 23
NC
COM
NO
31 32 33
NC
COM
NO
2 3
B
A
BGND
1 2 3 4 5 6 7 8
1 2 3 4 5 6
1 2 3 4
1 2 3 4
1 2
1 2 3 4 5
1
XDI
XAI
XSMC
XSTO
XRO1
XRO2
XRO3
XD2D
XAO
SDCS-DSL-Hxx
XENC (Encoder)
XD24
XDO
F100
F101
F102
C1
U1
V1
W1
D1
F+ F-
X10:
max 230 V
(H5) X2:
(H4) X52:
5
1
BL_CONH01_002_allocation_b.ai
X51
1 2
1 2 3
1 2 3
X52
X53
X200
J1
ON
XSMC
XTAC
X13
PANEL
X205
MEMORY
UNIT
V301
X208
X38
X12
X14
XC12
XC13
XS13
OPTION
X200
1
3
4
6
DCSLink
OPTION
XRO1
XRO2
XRO3
XENC
cable shield grounding plate
J4
XSTO
XDI
XDIO
J3
J6
J5
J1
XD24
XD2D
XAO
XAI
J2
J7
CONTROL
SLOT1
Battery
SLOT2
FAN
SAFETY
SLOT3
DCS880 module:
Terminal allocation
Aux.
supply
Fan
SDCS-CON-H: Connector allocation
SDCS-CON-H: Terminal allocation
DCS880 Accessories
Cross section areas - Thightening torques
Recommended
cross-sectional area to
DINVDE 0276-1000
and
DINVDE 0100-540 (PE)
trefoil arrangement, up to 50°C
ambient temperature.
Armature:
Converter type
C1, D1
U1, V1, W1
PE
I
DC
[A-]
1
[mm²]
(2.)
[mm²]
Iv
[A~]
[mm²]
[mm²]
[Nm]
DCS880-S0x-0025-xx
25
1 x 6
-
21
1 x 4
1 x 10
1 x M6
6
DCS880-S0x-0050-xx
50
1 x 10
-
41
1 x 6
1 x 10
1 x M6
6
DCS880-S0x-0075-xx
75
1 x 25
-
61
1 x 25
1 x 16
1 x M6
6
DCS880-S0x-0100-xx
100
1 x 25
-
82
1 x 25
1 x 16
1 x M6
6
DCS880-S0x-0150-xx
150
1 x 35
-
114
1 x 35
1 x 16
1 x M10
25
DCS880-S0x-0200-xx
200
2 x 35
1 x 95
163
2 x 25
1 x 25
1 x M10
25
DCS880-S0x-0250-xx
250
2 x 35
1 x 95
204
2 x 25
1 x 25
1 x M10
25
DCS880-S0x-0300-xx
300
2 x 70
1 x 95
220
2 x 50
1 x 50
1 x M10
25
DCS880-S0x-0320-xx
320
2 x 70
1 x 95
220
2 x 50
1 x 50
1 x M10
25
DCS880-S0x-0350-xx
350
2 x 70
-
286
2 x 50
1 x 50
1 x M10
25
DCS880-S0x-0450-xx
450
2 x 95
-
367
2 x 95
1 x 95
1 x M10
25
DCS880-S0x-0520-xx
520
2 x 95
-
424
2 x 95
1 x 95
1 x M10
25
DCS880-S0x-0650-xx
650
2 x 120
-
555
2 x 120
1 x 120
1 x M12
50
DCS880-S0x-0680-xx
680
2 x 120
-
555
2 x 120
1 x 120
1 x M12
50
DCS880-S0x-0820-xx
820
2 x 150
-
669
2 x 120
1 x 120
1 x M12
50
DCS880-S0x-0900-6/7
900
4 x 95
3 x 150
734
4 x 70
1 x 150
2 x M12
50
DCS880-S0x-1000-xx
1000
2 x 185
-
816
2 x 150
1 x 150
1 x M12
50
DCS880-S0x-1190-xx
1190
4 x 120
-
971
4 x 95
2 x 95
2 x M12
50
You will find instructions on how to calculate the PE conductor’s cross-sectional area in VDE 0100 or in equivalent national standards.
We would remind you that power converters may have a current-limiting effect.
Excitation:
Size
H1
H1
H2
H3, H5, H6
H4
H5
DC output current
6 A
12 A
18 A
25 A
30 A
max. cross sectional area
6 mm²/ AWG 10
6 mm²/ AWG 10
6 mm²/ AWG 10
6 mm²/ AWG 10
6 mm²/ AWG 10
min. cross sectional area
1 mm²/ AWG 16
2.5 mm²/ AWG 13
4 mm²/ AWG 11
6 mm²/ AWG 10
6 mm²/ AWG 10
Tightening torque
1.5 ... 1.7 Nm
cable shield grounding plate