Chapter 4 - Signals and Troubleshooting
IV F
4 - 6
DCS 600
Operating Instructions
Code
seven
segm.
display
Text on
LCD of control panel
CDP 312
(or DRIVES WINDOW)
Definition /
Action
Status
signal
(FAULT_WORD_
1/2/3)
Remark
F
23
23 MOT STALL
Motor stalled
While starting the motor
the
current exceeded
the value of parameter
[P 28.17]
for a time
longer than parameter
[P 28.15]
and
the
speed feedback value was below parameter
[P 28.16]
.
Check: - Motor stalled?
- Load changed during start?
- Correct field current?
- Current/torque limitation;
- Parameter settings
[P 15.08]
.
9.02 bit 14
(3)
F 27
27 MOT2 LOAD
Overload of MOTOR 2
(Thermal model
2
).
{see Fault Code
F 7
}
9.01
bit 9
(2)
F 28
28 ARM OVOLT
Armature (DC circuit) overvoltage
Check: - Setting of param.
[P 28.22]
suitable
for the system configuration?
- Setting of field current and actual
value as well as the complete
field supply (FIELD EXCITER);
- Was the motor accelerated by
the load?
- Speed scaling;
- Armature voltage feedback;
- Connections between SDCS-
CON-2 and SDCS-PIN boards;
- Coding of voltage evaluation on
SDCS-PIN-xx board.
9.01
bit 2
(1)
F 29
29 MAIN UVLT
Mains supply undervoltage
(AC)
; setting via
parameters
[P 40.01]
or/ and
[P 40.02]
Check: - Is the mains voltage within the
admissible tolerance?
- Did the mains contactor close
and open?
- Voltage scaling via parameter
[P 42.06]
rated line voltage
correct?
- Connections between SDCS-
CON-2 and SDCS-PIN-xx boards;
- Coding of voltage measurement
on SDCS-PIN-xx board.
9.01 bit 11
(3)