Chapter 2 - Start-Up Instructions
IV F
2 - 14
DCS 600 Operating Instructions
Drive must not turn!
Do not preset an external reference!
15.02 = 3
Activate the current controller’s auto-tuning function.
Start the next two steps within the next 20 seconds!
Switch ON power.
DANGER
: System components now energized!
Start drive.
When the display shows
”0”
(zero) stop drive; it may happen that the unit runs
armature-circuit current since EMF control is active.
If the unit aborts the auto-tuning routine with the signal 15.02 = -1, the probable
cause of this can be read out of Parameter
6.02
and has to be eliminated as far
as possible (supply, switching sequence etc.).
Afterwards repeat the auto-tuning routine.
If necessary, perform manual balancing.
Switch OFF power!
Read out values of:
41.11
= .........
41.12
= .........
43.02
= .........
43.03
= ............
43.06
= .........
Use values of
41.11
and
43.06
from the first auto-tuning routine.
Re-activate the field unit used by entering:
a)
15.05 = 1
or
b)
15.05 = 2
and install the supply fuses removed before!