Page 46
© 2021 ABB. All rights reserved.
Examples in the table are shown for conditions on the b circuit of the QS982A card. The same rea-
soning applies when the
“
a
”
circuit LEDs are illuminated.
LED Display
Conditions
Action Required
All OK
None
Circuit Placed in
Standby
None depending on desired state of circuit b. Standby state
can be set using the QS941 controller or web browser.
Loss of comm.
Check seating on Alarm card and converter card
Ground fault
Check 5 pin protectors and faults to ground
Overcurrent or under
voltage
Check output lines for shorts to each other
OV or internal failure
Replace unit
Thermal Alarm
Solve Thermal problem
card not powered or
input
Check source voltage
Lamps test
requested from
controller
Observe Lamp Test
Содержание CPS3200U
Страница 1: ...Page 1 2021 ABB All rights reserved PRODUCT MANUAL ...
Страница 12: ...Page 12 2021 ABB All rights reserved This page intentionally left blank ...
Страница 17: ...Page 17 2021 ABB All rights reserved Figure 2 Capacitance Safety Limits ...
Страница 20: ...Page 20 2021 ABB All rights reserved This page intentionally left blank ...
Страница 22: ...Page 22 2021 ABB All rights reserved This page intentionally left blank ...
Страница 33: ...Page 33 2021 ABB All rights reserved Step Action 2 ...
Страница 34: ...Page 34 2021 ABB All rights reserved Step Action Slide the filter in to the filter bracket 4 ...
Страница 43: ...Page 43 2021 ABB All rights reserved Step Action 14 ...
Страница 48: ...Page 48 2021 ABB All rights reserved ...
Страница 51: ...Page 51 2021 ABB All rights reserved 10 Maintenance ...
Страница 52: ...Page 52 2021 ABB All rights reserved This page intentionally left blank ...
Страница 62: ...Page 62 2021 ABB All rights reserved This page intentionally left blank ...