After the converters are recognized to be in a normal state, one should confirm the proper operation
of the alarm contact closures. If alarm wiring is correct:
1.
The loss of A or B input power should result in the assertion of a Power Minor.
2.
The loss of both A and B input power, which will result in a loss of service, should result in a Power Major and a
Power Minor.
3.
If a controller is installed in the system then it will demonstrate an alarm state by turning the display red. Using
the buttons on the keypad the specific alarm can be retrieved by pressing the Back Arrow, When
the
system returns to normal function the display will be green.
To connect CPS2300U shelves to an IP Drop, follow these steps to install QS941A Ethernet module.
Step
Action
2.
completed.
3.
Replace the cover over the right hand end of the shelf.
Fan Shelf
Содержание CPS3200U
Страница 1: ...Page 1 2021 ABB All rights reserved PRODUCT MANUAL ...
Страница 12: ...Page 12 2021 ABB All rights reserved This page intentionally left blank ...
Страница 17: ...Page 17 2021 ABB All rights reserved Figure 2 Capacitance Safety Limits ...
Страница 20: ...Page 20 2021 ABB All rights reserved This page intentionally left blank ...
Страница 22: ...Page 22 2021 ABB All rights reserved This page intentionally left blank ...
Страница 33: ...Page 33 2021 ABB All rights reserved Step Action 2 ...
Страница 34: ...Page 34 2021 ABB All rights reserved Step Action Slide the filter in to the filter bracket 4 ...
Страница 43: ...Page 43 2021 ABB All rights reserved Step Action 14 ...
Страница 48: ...Page 48 2021 ABB All rights reserved ...
Страница 51: ...Page 51 2021 ABB All rights reserved 10 Maintenance ...
Страница 52: ...Page 52 2021 ABB All rights reserved This page intentionally left blank ...
Страница 62: ...Page 62 2021 ABB All rights reserved This page intentionally left blank ...