Page 16
© 2021 ABB. All rights reserved.
•
Insulation on field
-
wired conductors should be rated no less than 90° Celsius. Wire conductor size should be
sized per electrical codes for 75° Celsius wire, and based on the ampacity of the associated protection device.
Wiring internal to enclosed equipment cabinets should be rated at 105° Celsius (minimum).
•
Torque electrical connections to the values specified on labels or in the product documentation.
•
Input cables must be dressed to avoid damage to the conductors (caused by routing around sharp edges or
routing in areas where wires could get pinched) and undue stress on the connectors.
•
Alarm contacts on the office alarm connector (TB1) are not fused within the distribution panel; therefore, current
limiting protection for these contacts must be provided by external circuits. Maximum ratings for alarm
connections are 60Vdc and 0.5 amperes. Exceeding these maximum ratings could result in fire or damage to the
unit.
•
Fuse and/or circuit breaker loads must not exceed 80% of the fuse and/or circuit breaker current rating.
Distribute loads across the panel.
•
The short circuit current capability of the battery input to the panel must not exceed 10,000A.
•
DC branch circuits to this equipment must be protected with either fuses or circuit breakers. Refer to the
equipment ratings to assure rating of equipment will not exceed 80% of the value of the protector chosen.
•
For applications in cabinets, huts, vaults, and central offices, the CPS3200U mounting framework must be
connected to the system integrated ground grid.
•
Installing fuses or circuit breakers not specified for use in these modules may result in injury to service personnel
or equipment damage. Use only replacement parts listed in this manual and on the equipment drawings.
•
The telecom
-
type (e.g., GMT type) fuses can produce sparks during interruption or clearing of a fault on a high
energy circuit. Use only fuses provided with safety caps for this type of circuit. Installing telecom
-
type fuses not
equipped with safety caps may result in injury to service personnel.
•
The designed capacitance b/
-
190V RFT
-
V conductors is 2.2uF and the measured capacitance between
+/
-
190V and earth is 4.4uF. DO NOT add capacitance to the system to reach values that exceed safety limits per
the following figure:
Содержание CPS3200U
Страница 1: ...Page 1 2021 ABB All rights reserved PRODUCT MANUAL ...
Страница 12: ...Page 12 2021 ABB All rights reserved This page intentionally left blank ...
Страница 17: ...Page 17 2021 ABB All rights reserved Figure 2 Capacitance Safety Limits ...
Страница 20: ...Page 20 2021 ABB All rights reserved This page intentionally left blank ...
Страница 22: ...Page 22 2021 ABB All rights reserved This page intentionally left blank ...
Страница 33: ...Page 33 2021 ABB All rights reserved Step Action 2 ...
Страница 34: ...Page 34 2021 ABB All rights reserved Step Action Slide the filter in to the filter bracket 4 ...
Страница 43: ...Page 43 2021 ABB All rights reserved Step Action 14 ...
Страница 48: ...Page 48 2021 ABB All rights reserved ...
Страница 51: ...Page 51 2021 ABB All rights reserved 10 Maintenance ...
Страница 52: ...Page 52 2021 ABB All rights reserved This page intentionally left blank ...
Страница 62: ...Page 62 2021 ABB All rights reserved This page intentionally left blank ...