C80
User Guide
Client/ Subscriber
Server/ Publisher
Value/ Comments
If SVC (B41/42) is supported
M14
Multicast SVC
n
M15
Unicast SVC
n
For all ieds
M16
Time
Y
Time source with required accuracy
shall be available.
Only Time Master are SnTp (Mode 4
response) time server.
All other Client / Server devices
require SnTp (Mode 3 request) clients
Y = service is supported
n or empty = service is not supported
ACSI Service Conformance Test
The ACSI service conformance statement is defined below (depending on the statements in ACSI Basic
Conformance Statement and in ACSI Models Conformance Statement).
Ed.
Services
AA: TP/MC Client (C) Server (S)
Comments
Server
S1
1,2
GetServerdirectory
(LOGiCAL-deViCe)
Tp
Y
Application Association
S2
1,2
Associate
Y
S3
1,2
Abort
Y
S4
1,2
Release
Y
Logical Device
S5
1,2
GetLogicaldevicedirectory
Tp
Y
Logical Node
S6
1,2
GetLogicalnodedirectory
Tp
Y
S7
1,2
GetAlldataValues
Tp
Y
Data
S8
1,2
GetdataValues
Tp
Y
S9
1,2
SetdataValues
Tp
Y
S10
1,2
Getdatadirectory
Tp
Y
S11
1,2
Getdatadefinition
Tp
Y
Data Set
S12
1,2
GetdataSetValues
Tp
Y
S13
1,2
SetdataSetValues
Tp
n
S14
1,2
CreatedataSet
Tp
n
S15
1,2
deletedataSet
Tp
n
S16
1,2
GetdataSetdirectory
Tp
Y
Содержание CoreSense M10
Страница 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Страница 8: ...Page intentionally left blank ...
Страница 18: ...Page intentionally left blank ...
Страница 24: ...Page intentionally left blank ...
Страница 26: ...22 User Guide Figure 19 Selecting an input channel ...
Страница 36: ...Page intentionally left blank ...
Страница 44: ...Page intentionally left blank ...
Страница 56: ...52 User Guide ...
Страница 62: ...Page intentionally left blank ...
Страница 66: ...Page intentionally left blank ...
Страница 107: ......