A ppendix A
Modbus
The RS-485 and Modbus default settings can be modified using the web interface.
NOTICE
For best results it is recommended to configure the Modbus master with a timeout of
10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
The Modbus slave ID is 1.
RS-485 configuration
Baud rate
9600
data Bits
8
Stop bits
1
parity
none
Flow control
none (only none is supported)
TCP configuration port
Modbus TCp
502/tcp