The Synchronize Views dialog shows all common objects for the selected bay, voltage
level or substation object. A column is shown for each created view. By selecting and
clearing the check boxes, you can decide which objects are shown in different views.
Data connection
3.6.
General about Data connection
3.6.1.
The Data Connection function is used to connect the substation structure objects to the
communication structure. Process data values based on the communication structure
objects are used to update the symbol states in HMI. It is also used to get object
descriptions based on the substation structure names to the alarm and event lists.
Any data object that has event class defined in the communic-
ation structure, must be linked to the substation structure to
get the proper description to the alarm and event.
Before you can use the Data connection function, create the communication structure,
see 3.4.1, Creating substation and communication structures with SCL descriptions or
connectivity packages.
To connect the substation structure objects to the communication structure:
1.
In the Substation structure select a Substation, Bay, or Voltage level object and
right-click it. Select Data Connection to open the Data connection function.
The objects in the substation structure are shown on the left side of the Data connec-
tion window. The logical nodes that can be attached to the objects are shown on the
right side of the Data connection window.
2.
Click a substation structure object on the left side of the Data connection window.
The logical nodes that can be attached to the objects are listed in the structure on
the right side of the window.
3.
Double-click the logical node to attach/detach it to the correct substation structure
object.
4.
Click OK to save the changes.
37
COM600 series, Version 4.1
1MRS756740
HMI Configuration Manual
Содержание COM600 series
Страница 1: ...COM600 series Version 4 1 HMI Configuration Manual...
Страница 2: ......
Страница 64: ...64...