2.
Connect bays to busbars. Select a bay, right-click it and select Connect to a Busbar
from the menu.
3.
In the configuration dialog, select the corresponding switchgear and the busbar
object to connect them.
4.
If you need to connect a bay to another directly, select a bay, right-click it, and select
Connect to a Bay.
By doing this the bays will be connected via regular line.
The SLD Editor shows the lines between the bays and
the busbar connected to the same point in the busbar.
However, the lines are drawn to separate locations in
HMI.
5.
If you want to fine-tune the SLD Editor layout for the connection lines, you can add
a StopAt object from menu of the line. Move the StopAt point to the correct location
in the busbar.
29
COM600 series, Version 4.1
1MRS756740
HMI Configuration Manual