Do not add connectivity nodes to the connection between
the busbar and the bay switchgears.

Do not add connectivity nodes between the earth symbol
and the switchgear object (disconnector).

To connect a power transformer to another bay, create a
connectivity node in the target bay (not in the bay where
the power transformer is located).

Default relative sizes of the symbols can be configured
using the Settings tool of the Gateway object. Default
values can be overriden for individual symbol instances
with the Relative Size property of the symbol instance.
This makes it possible to have individual sizes for sym-
bols in the SLD.

5.

Add Via points, if you want the line to follow a certain route.

6.

Connect objects

Activate the Direct Link tool from the tool bar.

Link two objects together by selecting their link points.

22

1MRS756740

COM600 series, Version 4.1

HMI Configuration Manual

Содержание COM600 series

Страница 1: ...COM600 series Version 4 1 HMI Configuration Manual...

Страница 2: ......

Страница 3: ...on structures with SCL descriptions or connectivity packages 15 3 4 2 Creating substation structure manually 15 3 4 3 Adding Gateway object 16 3 4 4 Adding Substation 17 3 4 5 Adding voltage level obj...

Страница 4: ...n 45 3 12 Customizing IED parameter settings 46 3 13 Disturbance data upload 50 3 14 Project specific localization 51 Appendix 1 52 Single Line Diagram symbols 52 Appendix 2 56 SAB600 Toolbar 56 Appen...

Страница 5: ...ll be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This...

Страница 6: ...s thorough information on Grid Automation Controller COM600 later referred to as COM600 Human Machine Interface HMI and the central concepts related to it Information in this manual is intended for op...

Страница 7: ...hat point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The corresponding icons should be interpreted as follows...

Страница 8: ...the IEC 61850 protocol Intelligent Electronic Device Representation of a group of functions Each function is defined as a logical node A physical device consists of one or several LDs Logical Device L...

Страница 9: ...ther GW Human Machine Interface HMI International Electrotechnical Commission IEC Intelligent Electronic Device IED LON Application Guideline for substation automation LAG Local Area Network LAN Logic...

Страница 10: ...Operator s Manual 1MRS756739 COM600 Data Historian Operator s Manual 1MRS755001 COM600 Sequence Control Configuration Manual 1MRS756566 DNP LAN WAN Master OPC 1MRS756567 DNP Serial Master OPC 1MRS755...

Страница 11: ...PA Master OPC 1MRS755497 SPA Router OPC Document revisions 1 11 History Product revision Document version date Document created 3 3 A 13 2 2009 Document revised 3 4 B 06 11 2009 Document revised 3 5 C...

Страница 12: ...plications in ANSI standard based utility power networks Overview of COM600 2 2 COM600 provides gateway functions for mapping signals between protection and control IEDs in industrial or utility subst...

Страница 13: ...ices are displayed on the HMI Single line diagrams can be used to view any available measured values from the process devices Predefined user account 2 3 The predefined COM600 user account also works...

Страница 14: ...o the following 1 Prepare the communication structure as instructed in COM600 User s Manual 2 Make sure that you have the necessary connectivity packages or SCL description files that can help you in...

Страница 15: ...specify incoming outgoing feeders and so on by modifying or adding objects Additionally you might need to create busbar connections see 3 4 2 Creating substation structure manually 6 Download the con...

Страница 16: ...LD settings for example fonts and colors see 3 6 2 Settings Adding Gateway object 3 4 3 To link the Gateway object to the substation structure 1 Select the Gateway object in the Communication structur...

Страница 17: ...enabled True False Default True Watch Dog Enabled Defines if audio alarm is enabled for the Web HMI clients True False Default True Web Client Audio Alarm External Watchdog The full path of the comman...

Страница 18: ...tage level objects have to be unique 4 Modify voltage level properties if necessary The object properties for voltage level are presented in Table 3 4 5 1 Table 3 4 5 1 Object properties for voltage l...

Страница 19: ...tor see 3 5 1 Using the SLD Editor Single Line Diagram 3 5 Using the SLD Editor 3 5 1 To open the SLD Editor select substation voltage level bus or bay object and right click them Then select SLD Edit...

Страница 20: ...ate a diagram with the SLD Editor 1 In the Symbols view click the tabs to view the different sets of symbols see Fig ure 3 5 1 2 2 Click a symbol you want to use and drag it with the mouse to the Sing...

Страница 21: ...formers and power transformers 2 Rename the primary object using the name property in the property grid This name is used in HMI for the object 3 Add primary Connection objects for example feeders ear...

Страница 22: ...relative sizes of the symbols can be configured using the Settings tool of the Gateway object Default values can be overriden for individual symbol instances with the Relative Size property of the sy...

Страница 23: ...tionally you can add for example a Bay Switch indicator annotations and measurement text boxes Bay_SLD png Figure 3 5 1 3 The Bay SLD view 23 COM600 series Version 4 1 1MRS756740 HMI Configuration Man...

Страница 24: ...ment text box 1 Right click the object and select Configure Measurement function from the menu 2 Using the configuration dialog select the measurements to be shown in HMI If the IED does not provide a...

Страница 25: ...sent to the pro cess Optionally an indication can be shown The Push Button With Value can be used to send an integer or a float value to a certain data object After clicking the button the value to b...

Страница 26: ...tart and end objects only one start and end point is allowed 2 Add a Connectivity Node one connectivity node is enough to connect all bays to this busbar 3 Connect the objects Activate the Direct Link...

Страница 27: ...Coloring is automatically configured when the SLD is drawn Connecting switchgear objects together specifies their electrical connections which is used during runtime to calculate the proper coloring S...

Страница 28: ...rules so that the busbar coloring works correctly A measurement value must be greater than the configured value A data object value is equal to the configured value A data object value is unequal to t...

Страница 29: ...ect Connect to a Bay By doing this the bays will be connected via regular line The SLD Editor shows the lines between the bays and the busbar connected to the same point in the busbar However the line...

Страница 30: ...g Figure 3 5 1 8 The voltage level SLD view Substation SLD To create a substation SLD 1 If you have more than one voltage level object drag the objects to correct locations in the SLD 30 1MRS756740 CO...

Страница 31: ...o a bay function from the menu 3 Using the configuration dialog you can select winding and the target bay connectivity node 4 Add Station switch indicator local remote Configuration To configure the S...

Страница 32: ...information SPS CDC from the communication structure to the substation SLD_Editor png Figure 3 5 1 9 Substation SLD view 32 1MRS756740 COM600 series Version 4 1 HMI Configuration Manual...

Страница 33: ...nsion objects such as different types of buttons are view specific and can only be modified in the current view Master View The Master View configuration is used for all views by default when a custom...

Страница 34: ...vel object specifies which bays are shown for that voltage level on the substation SLD Substation View configured on a bay object specifies which conducting equipment is shown for that bay on the subs...

Страница 35: ...substation extension objects can be added to each view and they are bound to the view they are created on bayViewCreated png Figure 3 5 2 2 An example of a Bay View Depending on the level you can cre...

Страница 36: ...e it on demand when the operator opens the Bay View If the Substation View with the bay has been defined the on demand Bay View is generated based on that If the Substation View does not contain the b...

Страница 37: ...re you can use the Data connection function create the communication structure see 3 4 1 Creating substation and communication structures with SCL descriptions or connectivity packages To connect the...

Страница 38: ...evels Default Colors You can modify the default colors of devices Fonts You can modify the font definitions Measurement Precisions You can adjust the precision settings of the measurements Bus Bar Col...

Страница 39: ...t page configuration Table 3 7 1 Properties for measurement configuration Description Property Item path from IED to data attribute Source Defines whether the description is shown Show Description If...

Страница 40: ...to_library png Figure 3 8 2 Adding files to the Document Library 3 Select a file to be added to the library add a caption for the selected file and click Apply Editing Document Library references You...

Страница 41: ...s by adding or removing rows or columns and re positioning them Bind cells to a data source for a dynamic status display Save existing tables as templates for later use Alarm and event handling 3 10 G...

Страница 42: ...event class you want to add 4 The new event class appears in the Process Definitions below the selected event group Enter a unique name for the event class by right clicking it and selecting Rename Th...

Страница 43: ...hen importing IED configurations from connectivity packages or IED SCL description files event definitions are linked to data objects by default For example switch position data object CSWIx Pos is li...

Страница 44: ...both for indication and control events or only one of them These properties define the event classes that are used with the data object Configuring event type filters 3 10 5 The Event Type Filter con...

Страница 45: ...ability performance and real time function ality to provide an excellent platform for process information management The data historian can be used for accurate process performance monitoring by follo...

Страница 46: ...the IED that supports the parameter information must be installed With the Parameter Selection tool of SAB600 you can select the parameters that are shown in the Parameter Setting view in HMI This opt...

Страница 47: ...ity package is available or the connectivity package does not contain a specific parameter for your needs you can add new parameters using the Add Parameter Form To add a new parameter 1 Click Add Par...

Страница 48: ...le LD0 PHIPTOC1 StrValMult setMag f The syntax is Logical Device Logical Node Data Object Data Attribute Adding new parameters for Modbus IEDs If a connectivity package is not available for Modbus IED...

Страница 49: ...meter to the Parameter Filtering view Add Parameter for Modbus IED bmp Figure 3 12 3 Adding a parameter for Modbus IED Exporting parameters You can export the information of the selected parameters to...

Страница 50: ...is implemented to each OPC Server Protocol and device specific differences are hidden from the OPC client The files are stored temporarily to the COM600 computer where they can be transferred further...

Страница 51: ...ize objects in the substation structure or communication tree 1 Select the object you want to modify 2 Right click the object and select Rename 3 Modify the name of the object To localize object prope...

Страница 52: ...on off auto matic manual X not X and so on It can also be used to send a command Two State Switch Hyperlink to external information source such as a web page or a local file on COM600 Files should be...

Страница 53: ...tiple State Button ViaPoint Connectivity Node Circuit breaker Inter mediate position Circuit breaker Open position Circuit breaker Closed position Circuit breaker Bad faulty position Disconnector Inte...

Страница 54: ...ndings and no Tap Changer Primary winding on top Second ary winding below All composing elements exist as individual sym bols Power Transformer with two Windings and Tap Changer Primary winding on top...

Страница 55: ...actor Generator Motor In feeder Out feeder Earth symbol Bay Switch Indicator Station Switch Indicator Display Voltage Five State Switch Left Earthed Five State Switch Right Earthed Power Cable Gas Ins...

Страница 56: ...es Selects an object in the SLD Editor window Enables navigation of the SLD Editor window using a mouse Displays a grid view in the SLD Editor window Zooms in out the SLD Editor window Opens the direc...

Страница 57: ...bstation structure based on identification for the events and alarms Table A3 1 Logical node classes and primary objects Comment Mandatory LN Class Primary object Substation Loc data used for sta tion...

Страница 58: ...ls data used for interlock ing status in control dialogs CILO PTRC SIML CALH G Disconnector DIS XSWI Pos data used for switch device position and control Mandatory CSWI RREC Rel data used for syn chro...

Страница 59: ...G Q Power Overhead Line LIN ZLIN CALH G Rotating Reactive Component RRC ZRRC CALH G Surge Arrestor SAR ZSAR CALH G Thyristor controlled frequency converter TCF ZTCF CALH G Thyristor controlled reactiv...

Страница 60: ...incoming feeder and generator Incoming Feeder Line IFL CALH G Q Powered rules for the Generator can be con figured in the SLD editor See 3 5 1 Con figuring the powered state for incoming feeder and g...

Страница 61: ...h indicator configuration 25 Bay View 35 busbar adding 19 busbar SLD 26 button configuration 25 C configuration prerequisites 14 connectivity packages 15 creating substation structure 15 D Data connec...

Страница 62: ...teway 16 voltage level 18 P Parameter Filtering Tool 46 parameter settings customizing 46 S SCL descriptions 15 Single Line Diagram multiple views 33 symbols 52 SLD Editor using 19 SLD views Bay View...

Страница 63: ...substation structure creating 15 Substation View 33 V voltage level adding 18 object properties 18 voltage level SLD 28 63 COM600 series Version 4 1 1MRS756740 HMI Configuration Manual...

Страница 64: ...64...

Страница 65: ......

Страница 66: ...hts reserved ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 ABB Inc Distribution Automation 655 Century Point Lake Mary FL 32746 USA Tel 1 407 7...