Multiple SLD views
3.5.2.
COM600 HMI supports customized SLD views for substation, voltage level and bay
objects. By default, the different SLD views are based on the same master SLD config-
uration, Master View.
Additionally, it is possible to create a bay-specific Bay View, for example, to give more
detailed information about the bay. The Bay View overrides the Master View when the
SLD is opened from the bay object in HMI. The substation and voltage level SLDs
always show the bay SLD as in the Master View configuration.
The different views can be modified on each level and the modifications affect only the
selected view. However, modifications on the Master View affect all other views.
Extension objects, such as different types of buttons, are view-specific and can only be
modified in the current view.
Master View
The Master View configuration is used for all views by default, when a customized
Substation View or Bay View has not been configured. The Master View must always
contain all the primary substation elements required in all views. Primary substation
elements are conducting equipment, power transformers and connectivity nodes. Busbar
coloring is based on the Master View.
Substation View (optional)
The Substation View can be used to override the substation SLD in the Master View.
The Substation View contains substation and substation extension elements that are
shown in the substation SLD in COM600 HMI. With the Substation View configuration
it is possible to hide unnecessary elements from all levels.
33
COM600 series, Version 4.1
1MRS756740
HMI Configuration Manual