Hysteresis

Alarm On

Alarm Disabled

Alarm Enabled

Trip Point

Alarm Off

Delay Time

Process
Variable

1

2

3

4

5

6

7

Process variable goes above trip point but alarm is not activated because enable signal is low
(Alarm Disable)

.

Alarm Enable signal is switched ON by activation of milking system. Alarm delay timer started.

Process variable goes above trip point but alarm is not activated because alarm delay time has
not expired.

Alarm delay timer expires, alarm is now enabled. Alarm is activated because  process variable
is above trip point

.

Process variable goes below trip (hysteresis) point therefore alarm is de-activated.

Process variable goes above trip point, alarm is activated (alarm is enabled and delay time has
expired)

.

Alarm Enable signal is switched OFF by activation of refrigeration system. Alarm is disabled
immediately. Alarm de-activates.

1

2

3

4

5

6

7

Note.

Refer to Programming Guide (IM/C1900–PGR or IM/C1900–PGC) Section 3.4 for alarm configuration procedures.

4.1 Delayed High/Low Process Alarm – Fig. 4.1

The operation of a Delayed High/Low Process Alarm is identical to that of the Standard High/Low Process Alarm but the alarm

can be enabled/disabled by use of a digital signal.

The alarm state is held off whilst the enable signal is off and continues to be held off for a pre-configured period of time after the

enable signal is switched ON (irrespective of the process variable value). Once the pre-configured alarm delay time has expired,

the alarm operates in the same manner as a standard high/low process alarm.

Fig. 4.1 Delayed High/Low Process Alarm

4 ALARMS

Содержание C1900 Series

Страница 1: ...ch for or click on C1900 Circular chart recorder Datasheet DS C1900R EN C1900 Circular chart recorders and recorder controllers Installation Guide IM C1900 INS C1900 Circular chart recorders Operating...

Страница 2: ...roval of the Technical Publications Department Health and Safety To ensure that our products are safe and without risk to health the following points must be noted The relevant sections of these instr...

Страница 3: ...This Supplementary Manual provides an overview of the use of the C1900 Circular Chart Recorder on a Dairy Farm and describes the electrical connections and special alarm feature designed for this app...

Страница 4: ...arning light also located in the barn is illuminated if milk temperature and or time limits are exceeded An additional set of indicator and warning lights can be mounted in a more convenient location...

Страница 5: ...Red White Red White C1900 Milking System Power Supply A B E D C C1900 Connections A Analog input connection from tank RTD sensor B Analog input connection from return flowline RTD sensor C Digital in...

Страница 6: ...used for signal inputs and relay connections Connect the screen to the ground stud The terminal blocks can be removed from the main p c b when making connections Before removing any module note its po...

Страница 7: ...y Connections within Recorder 230 V AC Connections 115 V AC Connections 24 V AC DC Connections Terminal Block 2 Channel 2 Green High Voltage Digital Interface Card See Fig 2 1 for cover removal detail...

Страница 8: ...2 1 dEGF Lower the chart clamp and press down firmly to ensure that the 2 locating pins pierce the paper 1 2 3 4 5 6 3 1 Fitting the Chart Fig 3 1 75 0 Raise pens Remove cap Fit new pen capsule ensuri...

Страница 9: ...enabled and delay time has expired Alarm Enable signal is switched OFF by activation of refrigeration system Alarm is disabled immediately Alarm de activates 1 2 3 4 5 6 7 Note Refer to Programming G...

Страница 10: ...A s e Y e l b a n E t f i L n e P d e l b a n E s m r a l A e p y T t n e m e g d e l w o n k c A e n o N e c r u o S k c A l a b o l G e n o N 1 A m r a l A 1 B m r a l A s m r a l A r e h t O l l A...

Страница 11: ...Sales Software Service...

Страница 12: ...ll rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden w...

Отзывы: