Control Terminals
1
2
3
4
5
6
7
8
9
10
11
V
Control
Terminal
Signal
1
+24V User Output, 100mA
2
Digital Input 1
3
Digital Input 2
4
Digital Input 3 /
Analog Input 2
5
+10VDC (10mA) 1kΩ
minimum Reference for
Potentiometer
6
Analog Input 1 /
Digital Input 4
7
0V common, internally
connected to terminal 9
8
Analog Output (0 to 10V)
Digital Output (0 to 24V)
20mA maximum
9
0V
10
Modbus RTU -
11
Modbus RTU +
RL1-A
Relay Common
RL1-B
Relay NO Contact
250Vac, 6A / 30Vdc, 5A
Additional Connection Examples
3-Wire Start/Stop with Forward/Reverse Terminal Control Mode (1103 = 0)
Digital input configuration when the drive is controlled using momentary push-buttons. It provides a general
purpose I/O setup with a momentary input for start, forward / reverse, stop interlock and an analog speed
reference.
9902 = 11
3-Wire Forward Reverse
A momentary input on terminal 2 will
start the drive in the forward direction
with a closed input on terminal 3.
A momentary open input to I/O
terminal 3 will stop the drive as
specified in 2101 (Stop Mode).
A momentary input on terminal 4 will
reverse the drive direction.
1 +24V User Input
2 Digital Input 1
4 Digital Input 3
3 Digital Inpu 2
5 +10 Volts
6 Analog Input
7 0 Volts
Start
Stop
Direction
Customizing your Application
Factory settings may give satisfactory performance however certain
adjustment.
Parameter
Name
Parameter
Adjustment
Minimum Frequency
Limit
2007
Minimum output frequency
Maximum
Frequency Limit
2008
Maximum output frequency
①
Primary Command
Source
1103
Selects the reference input for
the drive.
Digital Input
Function Select
9902
Defines the function of the digital
inputs
Stop Mode
2102
Select method of stopping
required when drive is disabled.
Acceleration Ramp
2202
Adjust as need for your
application. Short Acceleration
or Deceleration times may cause
excess motor current and may
result in it tripping or the motor
stalling.
Deceleration Ramp
2203
Analog Input Format
1300
Set as required by the application
(0-10V, 10-0V, 4-20mA)
Voltage Boost
2603
Any hard to start load will benefit
from voltage boost. Permits a
boost of up to 25% of full motor
voltage to be applied.
①
NOTE:
The Analog Input Value scales with the maximum output
frequency setting in 2008.
Example:
The motor will run at 1800 RPM with a 10V DC reference
and when parameter 2008 = 60 HZ.
Accessing Parameters and Program
Navigation
The parameters are arranged in Groups according the to the following structure.
Short Parameter
Group
Basic Setup Parameters
Long Parameter
Group
Sequential List all Parameters
Access to Display Group
Advanced Group
Advanced Motor Control
Read Only Display
Group
Parameter 0000 Par L Group
Parameter Navigation
•
Press and hold the NAVIGATE key for more than 1 second when the drive is displaying
STOP
.
The display changes to
PAr 5
, indicating the short (
S
) parameters group. Use the
(UP) and
(DOWN) keys to select between the
S
,
L
or
A
parameter groups.
•
To enter a parameter group, press and release the
(Navigate) key while the group letter is
flashing. Use the
(UP) and
(DOWN) keys to change to the desired parameter number.
•
To change parameter values, press and hold the
(Navigate) key then use the
(UP) and
(DOWN) keys to change to the required value. Press and release the
(Navigate) key
once more to store the change.
•
Press and hold the
(Navigate) key for more than 1 second to return to real-time mode. The
display shows
STOP
if the drive is stopped or the real-time information (e.g. speed, current or
power) if the drive is running.
•
To access Read Only Parameters, navigate to
PAr L
Group and scroll to Parameter 0000, then
press and release the navigate key.
Motor Nameplate Information
The EC Titanium Motor nameplate is located on the side of the motor and includes NEMA rating, appropriate marking, a type designation and a serial number, which allow
identification of each unit. The motor nameplate contains electrical information necessary for proper setup of a drive control.
SYNCHRONOUS RELUCTANCE MOTOR
FOR INVERTER USE ONLY
READ INSTRUCTIONS BEFORE INSTALLING.
PERMANENT MAGNET MOTOR. WHEN SHAFT IS
ROTATED, VOLTAGE WILL BE GENERATED AT
THE MOTOR TERMINALS.
LIRE LES INSTRUCTIONS AVANT L’INSTALLATION,
MOTEUR Á AIMANT PERMANENT. LORSQUE
L'ARBRE TOURNE, UNE TENSION SERA GÉNÉRÉE
AUX BORNES DU MOTEUR.
BALDOR- RELIANCE
ELECTRONICALLY PROTECTED MOTOR
FOR INDUSTRIAL USE
SHAFT GROUNDING BRUSH INSTALLED
NP3968A01C01
ABB MOTOR AND MECHANICAL INC., FORT SMITH, AR. MFG. IN U.S.A.
WARNING/AVERTISSEMENT
EC-Titanium
TM
BEARING
RATING
VOLTS
R.P.M.
SPEC.
ENCL.
CAT. NO.
CT
TO
HZ
FRAME
Ld (mH)
IP
DE
ODE
VPWM
TO
CHP
HZ
VT
MATCHED INV
FLA
RPM MAX
PH.
CLASS
HZ
BEMF VOLTS
SER.F.
NEMA NOM. EFF
INV TYP
Lq (mH)
SER#
TO
HZ
PF
Rs OHM
HP
35E5247Z715G1
-
2
145T
TEFC
54
460
2.2
1800
60
1.0
4000
3
F
12.95
246
91.4%
40C AMB - CONT
109.6
505.5
60
6
1
ECI14A2P2
6205
6205
133
60
60
EN/IEC60034-1;-5
LISTED
E46145
1
ECS100A4H2140FF4
2
3
5
6
9
10
8
11
7
ECI4A2P2
4
12
14
13
FERRITE ASSISTED
Region
Description
Factory Set Parameters
②
1
Catalog Number
2
General Motor Information
3
Motor Rated Amps
9906
4
BEMF (Back EMF) Voltage
9905
5
Motor Stator Resistance (Rs)
11201
6
Ld (mH) Motor Inductance (Lsd)
11203
7
Lq (mH) Motor q-axis Inductance (Lsq)
11206
8
Motor Rated Frequency
9907 (Rated Speed)
Motor Maximum Frequency
2208 (Max Speed)
9
Matched Inverter Model Number
10
PM Motor Warning Information
11
Shaft Ground Provision Marking
12
QR Code for motor information
13
CE Marking
14
UL Agency Listing
Additional Factory Preset Parameters
Start Stop Mode 1 = Coast to Stop
2102 = 1 Coast to stop
Minimum Speed
2007 = 15 HZ
Control Mode
9903 = 2 PM Control
Motor values shown on the nameplate are utilized for proper control and setup of a drive used to run the EC Titanium motor.
②
NOTE:
Integrated units are factory programmed and parameters do not need to be adjusted unless a software reset was implemented.