EC Titanium

TM

 Motor 

Installation and Maintenance

NEMA Frames 140 - 210

OVERVIEW

This manual contains general procedures that apply to Baldor EC Titanium Motor product and is not intended to include a comprehensive listing of all details for all procedures 
required for installation, operation and maintenance. Be sure to read and understand the Safety Notice statements in this manual. For your protection, do not install, operate or 
attempt to perform maintenance procedures until you understand the Warning and Caution statements. A Warning statement indicates a possible unsafe condition that can cause 
harm to personnel. A Caution statement indicates a condition that can cause damage to equipment.

The EC Titanium are IE5 efficient motor specifically designed for operation on adjustable speed permanent magnet ac drive controls and is not designed for across the line 
operation. Information required for proper control and setup of the separate drive is provided on the nameplate of the motor. Detailed information can be found in the EC Titanium 
Installation Manual MN451 available for download at http://www.baldor.com/support/product_manuals.asp. Be sure to read and understand all of the Safety Notice statements 
in MN451 EC Titanium Manual for your motor. The basic design includes Class F insulation, Class B temperature rise, 1.5 service factor motor only (1.0 SF integrated motor drive 
designs), 40°C ambient, continuous duty. Standard enclosures are totally enclosed fan cooled foot mounting. It is important that motors be installed in locations that are compatible 
with motor enclosure and ambient conditions. Improper selection of the motor enclosure and ambient conditions can lead to reduced operating life of the motor. Proper ventilation 
for the motor must be provided. Obstructed airflow can lead to reduction of motor life.

RECEIVING AND INSPECTION

The EC Titanium is thoroughly tested at the factory and carefully packaged for 
shipment. When you receive your motor or the integrated motor and drive, there are 
several things you should do immediately.
1.  Carefully Unpack the EC Titanium and check for any signs of damage. Notify the 

shipper immediately if any exist. 

2.  Check the motor and / or motor and drive rating label to ensure it is of the correct 

type and power requirements for the application. 

3.  If the motor is to be stored for several weeks before use, be sure that it is stored in 

a clean and dry environment and within a temperature range of –40°C to +60°C. 

4.  After storage or after unpacking and inspection to see that all parts are in good 

condition, rotate the motor shaft by hand to be sure there are no obstructions 
to free rotation. Motor leads must be isolated before the shaft will turn freely on 
permanent magnet motors.

On motors received from the factory with the shaft blocked, remove blocking before 
operating the motor. If motor is to be reshipped alone or installed to another piece of 
equipment, the shaft block must be installed to prevent axial movement and prevent 
brinelling of the bearings during shipment. 

SAFETY 

This equipment contains high voltage! Electrical shock can cause serious or fatal 
injury. Only qualified personnel should attempt installation, operation and maintenance 
of electrical equipment. Unsafe installation or use can cause conditions that lead to 
serious or fatal injury. Only qualified personnel should attempt the installation, operation 
and maintenance of this equipment. Be sure that you are completely familiar with safety 
standards for selection, installation and use of electric motors and generators and local 
codes and practices. Become familiar with the following:
• 

NEMA Publication MG-2, Safety Standard for Construction and guide for Selection, 
Installation and Use of Electric Motors and Generators

• 

IEC 60034−1 Electrical and IEC60072−1 Mechanical specifications

• 

NFPA 70® National Electrical Code (NEC) and local codes and practices

INSTALLATION OUTSIDE THE USA: 

Refer to MN408 and MN1383 for Compliance with European Directives. Copies are 
available at: http://www.baldor.com/support/product_manuals.asp 

MOTOR ENCLOSURE 

TEFC, totally enclosed motors are intended for use where moisture, dirt and/or corrosive 
materials are present. The EC Titanium motor only is rated for in indoor and outdoor 
locations. Integrated drive motor units with plastic covers are indoor use and not rated 
for direct sunlight or outdoor use. 

GENERAL 

The user must select a ac drive suitable for permanent magnet motor control. The 
ABB ACH580 is suggested and designed to automatically ID run the EC Titanium 
motor. For all other ac drive controls, ensure the drive is capable of permanent magnet 
motor control. Values identified on the motor nameplate must be available to enter into 
drive parameters. These are shown in the previous section of this guide and include 
Motor Rated Amps, Motor Back EMF Voltage, Rs (motor stator resistance), Ld (d-axis 
inductance), Lq (q-axis inductance) and motor rated frequency. Ensure the drive is sized 
properly for the current rating of the motor and set appropriate overcurrent protection 
suitable for this motor and its application. 

Speed Range

EC Titanium Motors are rated for a 10:1 Constant Torque Speed range below base 
speed. 140 and 180 Frame motors may be operated to a maximum safe speed of 4000 
RPM and 210 Frame motors 3000 RPM.

TESTING 

If the motor has been in storage for an extensive period or has been subjected to 
adverse moisture conditions, check the motor insulation resistance with a meg ohm 
meter. Depending on storage conditions it may be necessary to rotate or change rusted 
bearings. Contact your local sales office if resistance is less than 5 meg ohms. 

WARNING: Do not touch electrical connections before you first ensure that power 

has been disconnected. Electrical shock can cause serious or fatal injury. 

WARNING: Be sure the system is properly grounded before applying power. 

Electrical shock can cause serious or fatal injury. 

ELECTRICAL INSTALLATION 

This motor must be installed in accordance with National Electric Code, NEMA MG-2, 
IEC standards or local codes.

WARNING: EC Titanium permanent magnet motors can induce voltage and 

current in the motor leads by rotating the motor shaft. Electrical shock can cause 

serious or fatal injury. Therefore, do not couple the load to the motor shaft until 

all motor connections have been made. During any maintenance inspections, be 

sure the motor shaft will not rotate.

WIRING 

Connect the motor as shown in the connection diagrams. If this motor is installed as 
part of a motor control drive system, connect and protect the motor according to the 
control manufacturers diagrams. Refer to MN408 for additional details on lead marking. 
The wiring, fusing and grounding must comply with the National Electrical Code or 
IEC and local codes. When the motor is connected to the load for proper direction of 
rotation and started, it should start quickly and run smoothly. If not, stop the motor 
immediately and determine the cause. Possible causes are: low voltage at the motor, 
motor connections are not correct or the load is too heavy. Check the motor current 
after a few minutes of operation and compare the measured current with the nameplate 
rating. 

GROUNDING 

Ground the motor according to NEC and local codes. In the USA consult the National 
Electrical Code, Article 430 for information on grounding of motors and generators, and 
Article 250 for general information on grounding. In making the ground connection, the 
installer should make certain that there is a solid and permanent metallic connection 
between the ground point, the motor or generator terminal housing, and the motor or 
generator frame. In non-USA locations consult the appropriate national or local code 
applicable. 

Noise 

For specific sound power or pressure level information, contact your local sales office.

VIBRATION 

This motor is balanced to NEMA MG1, Part 7 standard. 

WARNING: Guards must be installed for rotating parts such as couplings, pulleys, 

external fans, and unused shaft extensions, should be permanently guarded to 

prevent accidental contact by personnel. Accidental contact with body parts or 

clothing can cause serious or fatal injury. 

DRAIN PLUGS 

One or more condensation drain fittings are provided on each endplate for various 
motor mounting configurations. The fittings allow drainage and prevent insertion of 
a 1mm wire probe per the IP54 rating requirements. To avoid condensation inside 
the motor, do not unpack until the motor has reached room temperature. (Room 
temperature is the temperature of the room in which it will be installed). The packing 
provides insulation from temperature changes during transportation.

MOUNTING 

Mount the motor on a foundation sufficiently rigid to prevent excessive vibration. 
Standard stock EC Titanium motors are provided with feet for mounting at any angle. 
Mounting provisions may also be provided on custom design motors to allow for direct 
coupled (c-face) or flange mounting at any angle. After careful alignment, bolt motor 
securely in place. For foot mounted motors, use shim to fill any unevenness in the 
foundation. Motor feet should sit solidly on the foundation before mounting bolts are 
tightened. 

EC Titanium Stock Motors are designed to be mounted by the “Mounting Feet”. Use 
appropriate hardware (not furnished). The motor should be installed in a location 
compatible with the motor enclosure and specific ambient. The motor must be securely 
installed to a rigid foundation or mounting surface to minimize vibration and maintain 
alignment between the motor and shaft load. Failure to provide a proper mounting 
surface may cause vibration, misalignment and bearing damage. All hold down bolts 
must be the correct grade for the type of mounting and must be torqued to their 
recommended value. The standard motor base is designed for horizontal or vertical 
mounting.
 

Содержание Baldor-Reliancer EC Titanium

Страница 1: ...ude Motor Rated Amps Motor Back EMF Voltage Rs motor stator resistance Ld d axis inductance Lq q axis inductance and motor rated frequency Ensure the drive is sized properly for the current rating of the motor and set appropriate overcurrent protection suitable for this motor and its application Speed Range EC Titanium Motors are rated for a 10 1 Constant Torque Speed range below base speed 140 an...

Страница 2: ...ow or the motor has been miss wired In any case immediately shut motor off and investigate the cause ROTATION To reverse the direction of rotation disconnect and lockout power and interchange any two of the three AC power leads for three phase motors For two phase four wire disconnect and lockout power and interchange the AC line leads on any one phase For two phase three wire disconnect and locko...

Страница 3: ... LED will change to constant on green Step 3 The display shows zero speed in Hertz as H 0 0 with the potentiometer turned to minimum If the display is not showing H change it with the navigate key Adjust the speed using the potentiometer the motor will accelerate to the speed set by the potentiometer up to the value set in parameter 2008 maximum frequency limit Step 4 Stop the motor disable the dr...

Страница 4: ... Setup Parameters Long Parameter Group Sequential List all Parameters Access to Display Group Advanced Group Advanced Motor Control Read Only Display Group Parameter 0000 Par L Group Parameter Navigation Press and hold the NAVIGATE key for more than 1 second when the drive is displaying STOP The display changes to PAr 5 indicating the short S parameters group Use the UP and DOWN keys to select bet...

Отзывы: