background image

EC Titanium

TM

 Quick Start Guide

Input Power & Control Connections

  

 Supply Voltage:

   - Single phase 115 or 230V

   - Three phase 230, 415, 460V

   - 50 / 60Hz

   - Use inputs L (L1) & N (L2)

     for single phase

   

Motor Connection:

   Factory wired do not disconnect

   

U V W

Fuse or MCB

check drive rating 

for cable sizing

AC Supply Voltage

Earth

L1 L2 L3

  

Status LEDs

 

  A1: Red = Trip

  Green = Healthy
  A2: Yellow = Alarm

A2 A1

  RJ45 Port

   Remote Keypad & PC Interface

  Control Terminals

   Terminals 1 to 11

  

Factory defaults settings:

 

 1. Connect a START/STOP switch to Terminal 1  2

    Close the contact START (enable) the drive

    Open the contact STOP (disable) the drive

 2. Connect 10k potentiometer on terminals 5, 6, & 7

      Vary the speed from 0 to max speed

1

2

5

6

7

Speed Reference

Command Input

&

Remote Keypad ECS100L

NAVIGATE

Used to display real-time information, 
to access and exit parameter edit 
mode and to store parameter changes.

UP

Increase speed in real-time mode or 
scroll through values in parameter edit 
mode.

DOWN

Decrease speed in real-time mode or 
scroll through values in parameter edit 
mode.

STOP

In normal application, when in Keypad 
mode, this button is used to stop a 
running drive. If in trip mode, the key is 
used to reset the drive.

START

When in keypad mode, the button is 
used to start a stopped drive or to 
reverse the direction of rotation.

NOTE:

   For keypad control set parameter 1103=1 and 9902 to 

the desired I/O configuration.

Quick Startup Guide

When delivered, the EC Titanium™ is pre-programmed to run from remote inputs wired to the terminal 
strip. This default digital input configuration provides a general purpose I/O setup with a hard wired start / 
stop enable, forward / reverse input and a selection between an analog speed reference or preset speed 
input.

Parameter 1103 = 0 defines control from the terminal strip (for Keypad Control 1103 =1) and Parameter 
9902 = 0 sets up the configuration for the inputs and outputs as shown below.

Step 1

Connect a control switch between the control terminals 1 and 2 and ensure that the contact 
is open (drive disabled). Connect a potentiometer (1kΩ min to 10 kΩ max) between terminals 
5 and 7 with the wiper to terminal   6 of the control terminal. With the potentiometer set to 
zero, switch on the supply to the drive.

Step 2

The status LED is slow flashing green and a connected EC100L Keypad will display 

STOP

.  

Close the control switch, terminals 1-2, the drive is now ‘enabled’ and the output frequency 
speed are controlled by the potentiometer. The status LED will change to constant on green.

Step 3

The display shows zero speed in Hertz as 

H 0

.

0

with the potentiometer turned to minimum. 

If the display is not showing 

H

, change it with the navigate key. Adjust the speed using the 

potentiometer, the motor will accelerate to the speed set by the potentiometer up to the 
value set in parameter 2008 (maximum frequency limit.)

Step 4

Stop the motor, disable the drive by opening the control switch (terminal 1-2).

Terminal Mode (1103=0)

Digital Input Function (9902=0)

2-Wire Forward Reverse

Active input across terminal 1 & 2 will cause 
the drive to run.

When terminal 3 is open the drive will 
operate in the forward direction. 

Closing input 3 reverses the commanded 
direction.

Closing terminal 4 will force operation at 
preset speed 1 (parameter 1202) or function 
as a jog command.

1    +24V User Input

2    Digital Input 1

4    Digital Input 3

3    Digital Inpu 2

5    +10 Volts

6    Analog Input

7    0 Volts

Stop - Run

Forward - Reverse

Analog - Preset 1

Speed Reference Input

Connection Example

Potentiometer
1-10K Ohm Potentiometer
Recommended (2 Watt Min.)

5    +10V O/P

6    Analog Input

7    0V

Analog Input
Analog Input Format (parameter 1300) 
selects Voltage or Current Source.
Voltage 0-10 or 10-0 Vdc
Current 0-20, 4-20 or 20-4 mA

6    Analog Input

7    0V

0-10V
4-20mA

Common

Keypad Operation

Setting parameter 

1103

 to a value of 1 enables keypad mode with 

forward direction only, while a value of 2 enables keypad mode with 
forward and reverse rotation.

Set parameter 

1100

 to 1 or 3 to enable the drive to start from the set 

keypad reference speed.

While the drive is stopped, press the 

STOP

 key. The value of the 

digital potentiometer will be displayed, indicating the target speed. 
Use the 

UP

 and 

DOWN

 keys to select the required target speed.

Press the 

STOP

 key to return to the real time display showing 

STOP

 

or the 

START 

key to start the drive ramping up to the target 

speed. To reverse direction, press the 

START

 key again.

Keypad Display Screens

Prior to operation the keypad will show 

STOP

, pressing the 

STOP

 

key allows setting the preset speed on the display (

H x.x

) While 

in operation the following displays can be accessed by briefly 
pressing the Navigate Key. 

 

  



STOP

Drive power applied and 
no Enable or Run signal

Drive Running

H 0

.

0

.

Output 
Frequency (Hz)

Press Navigate to 
select display

Press again to cycle 
display

A 0

.

0

.

Motor Current 
(Amps)

P 0

.

0

.

Motor Power
(kW)

Drive Running, Speed Reference = 0

Stndby

Enable / disable switch open drive will 
decelerate to stop and display shows 

STOP

A zero reference and enable/disable closed 
the display with show H 0.0 (0.0Hz)

>60 seconds at zero speed drive standby 
mode 

Stndby 

waiting for a speed 

reference

Содержание Baldor-Reliancer EC Titanium

Страница 1: ...ude Motor Rated Amps Motor Back EMF Voltage Rs motor stator resistance Ld d axis inductance Lq q axis inductance and motor rated frequency Ensure the drive is sized properly for the current rating of the motor and set appropriate overcurrent protection suitable for this motor and its application Speed Range EC Titanium Motors are rated for a 10 1 Constant Torque Speed range below base speed 140 an...

Страница 2: ...ow or the motor has been miss wired In any case immediately shut motor off and investigate the cause ROTATION To reverse the direction of rotation disconnect and lockout power and interchange any two of the three AC power leads for three phase motors For two phase four wire disconnect and lockout power and interchange the AC line leads on any one phase For two phase three wire disconnect and locko...

Страница 3: ... LED will change to constant on green Step 3 The display shows zero speed in Hertz as H 0 0 with the potentiometer turned to minimum If the display is not showing H change it with the navigate key Adjust the speed using the potentiometer the motor will accelerate to the speed set by the potentiometer up to the value set in parameter 2008 maximum frequency limit Step 4 Stop the motor disable the dr...

Страница 4: ... Setup Parameters Long Parameter Group Sequential List all Parameters Access to Display Group Advanced Group Advanced Motor Control Read Only Display Group Parameter 0000 Par L Group Parameter Navigation Press and hold the NAVIGATE key for more than 1 second when the drive is displaying STOP The display changes to PAr 5 indicating the short S parameters group Use the UP and DOWN keys to select bet...

Отзывы: