Planning the electrical installation
41
Selecting the power cables
General rules
Dimension the supply (input power) and motor cables
according to local
regulations
.
• The cable must be able to carry the drive load current. See the chapter
for the rated currents.
• The cable must be rated for at least 70
°
C (US: 75 °C [167 °F]) maximum
permissible temperature of conductor in continuous use.
• The conductivity of the PE conductor must be equal to that of a phase conductor
(ie. same cross-sectional area).
• 600 VAC cable is accepted for up to 500 VAC.
• Refer to the chapter
for EMC requirements.
Symmetrical shielded motor cable must be used (see the figure below) to meet the
EMC requirements of the CE and C-tick marks.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. Compared to a four-conductor system, the use of symmetrical
shielded cable reduces electromagnetic emission of the whole drive system as well
as motor bearing currents and wear.
The motor cable and its PE pigtail (twisted shield) should be kept as short as
possible in order to reduce electromagnetic emission.
Alternative power cable types
Power cable types that can be used with the drive are represented below.
Symmetrical shielded cable: three phase conductors and
a concentric or otherwise symmetrically constructed PE
conductor, and a shield
Motor cable
(also recommended for supply cabling)
PE conductor
and shield
Shield
Shield
Note:
A separate PE conductor is required if the
conductivity of the cable shield is not sufficient for the
purpose.
A four-conductor system: three phase conductors and
a protective conductor.
Shield
PE
PE
Allowed for supply cabling
PE
PE
Содержание ACSM1 Series
Страница 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Страница 2: ......
Страница 4: ......
Страница 14: ...Table of contents 14...
Страница 20: ...About this manual 20...
Страница 24: ...The ACSM1 04 24...
Страница 30: ...Planning the cabinet assembly 30...
Страница 46: ...Planning the electrical installation 46...
Страница 70: ...Maintenance 70...
Страница 84: ...Technical data 84...
Страница 90: ...Mains filters 90...
Страница 96: ...Dimension drawings 96 Frame size A...
Страница 97: ...Dimension drawings 97...
Страница 98: ...Dimension drawings 98 Frame size B...
Страница 99: ...Dimension drawings 99...
Страница 100: ...Dimension drawings 100 Frame size C air cooled module...
Страница 101: ...Dimension drawings 101...
Страница 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Страница 103: ...Dimension drawings 103 Frame size D air cooled module...
Страница 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Страница 106: ...Dimension drawings 106 Mains filters type JFI xx...
Страница 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Страница 110: ...Dimension drawings 110...
Страница 111: ......