Electrical installation
51
13. Ground the other end of the supply cable shield or PE conductor(s) at the
distribution board. In case a mains choke and/or a mains filter is installed, make
sure the PE conductor is continuous from the distribution board to the drive.
Grounding the motor cable shield at the motor end
For minimum radio frequency interference, ground the cable shield 360 degrees at
the lead-through of the motor terminal box
or ground the cable by twisting the shield so that the flattened shield is wider than
1/5 of its length.
360 degrees grounding
Conductive gaskets
a
b
b > 1/5 · a
Содержание ACSM1 Series
Страница 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 0 75 to 45 kW...
Страница 2: ......
Страница 4: ......
Страница 14: ...Table of contents 14...
Страница 20: ...About this manual 20...
Страница 24: ...The ACSM1 04 24...
Страница 30: ...Planning the cabinet assembly 30...
Страница 46: ...Planning the electrical installation 46...
Страница 70: ...Maintenance 70...
Страница 84: ...Technical data 84...
Страница 90: ...Mains filters 90...
Страница 96: ...Dimension drawings 96 Frame size A...
Страница 97: ...Dimension drawings 97...
Страница 98: ...Dimension drawings 98 Frame size B...
Страница 99: ...Dimension drawings 99...
Страница 100: ...Dimension drawings 100 Frame size C air cooled module...
Страница 101: ...Dimension drawings 101...
Страница 102: ...Dimension drawings 102 Frame size C for cold plate mounting...
Страница 103: ...Dimension drawings 103 Frame size D air cooled module...
Страница 104: ...Dimension drawings 104 Frame size D for cold plate mounting...
Страница 106: ...Dimension drawings 106 Mains filters type JFI xx...
Страница 108: ...Dimension drawings 108 Braking resistors type JBR xx...
Страница 110: ...Dimension drawings 110...
Страница 111: ......